Skip to main content
Mitsubishi Electric QY41P — Digital Output Modules

QY41P Transistor Output Module (Sink Type), 32 points, 0.1A/

MPNQY41P

Mitsubishi Q-series QY41P transistor output module (sink type), 32 points, 0.1 A/point, 12–24 VDC load voltage, photocoupler isolation, IP2X.

$120.00 – $241.64Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

QY41P key specifications
ParameterValue
Product typeTransistor Output Module (Sink Type)
Rated load voltage12-24VDC (+20/-15%)
Maximum voltage drop at ON0.1VDC (TYP.) 0.1A, 0.2VDC (MAX.) 0.1A
Dielectric withstand voltage560VAC rms/3 cycles (altitude 2000m)
Maximum load current0.1A/point, 2A/common
Leakage current at OFF0.1mA or less
Maximum inrush current0.7A, 10ms or less
Internal current consumption (5VDC)105mA (TYP. all points ON) (0.11A is shown on the rating plate of the module.)
Applicable connectorA6CON1, A6CON2, A6CON3, A6CON4 (optional)
Applicable wire size0.088 to 0.3mm2 (For A6CON1 or A6CON4)
External connections40-pin connector
Common terminal arrangement32 points/common (common terminal: A01, A02)

All specifications

QY41P additional specifications
ParameterValue
Applicable connector (terminal block converter module)A6TBXY36, A6TBXY54
Surge suppressorZener diode
Weight0.15 Kg
Shipping weight1.5 Kg
Isolation methodPhotocoupler
Protection degreeIP2X
Estimated lead timeUsually ships in 1 - 10 working days.
Operation indicatorON indication (LED)
Insulation resistance10M? or more by insulation resistance tester
Number of output points32 points
Number of occupied i (O points)32 points (I/O assignment is set as a 32-point output module.)

Product details

The QY41P is a 32-point transistor output module in the Mitsubishi Q-series, wired as sink type. Each point switches up to 0.1 A into a 12–24 VDC load (rated 12–24 VDC +20%/-15%), with a common return handling 2 A total. Photocoupler isolation separates the field side from the backplane; a Zener diode clamps inductive kickback at turn-off. The module draws 105 mA (typical, all points ON) from the 5 VDC backplane rail.

Integration notes

The module connects to the Q-series backplane via a 40-pin connector. Field wiring uses an optional A6CON1, A6CON2, A6CON3, or A6CON4 connector; wire size 0.088 to 0.3 mm² for the A6CON1 or A6CON4. If you need a terminal-block interface, the A6TBXY36 or A6TBXY54 converter module adapts the 40-pin connector to screw terminals. The common terminals are A01 and A02, shared across all 32 points. ON status is indicated per-point by LED.

Frequently asked questions

What are the key electrical ratings for the QY41P?

32 output points, sink type, rated load voltage 12–24 VDC (+20%/-15%), maximum load current 0.1 A per point and 2 A per common, leakage current at OFF 0.1 mA or less, maximum inrush current 0.7 A for 10 ms or less, maximum voltage drop at ON 0.2 VDC at 0.1 A.

How do I source the QY41P?

We source the QY41P to order against an RFQ. Typical lead time is 1–10 working days.

MPN