What the ratings mean for fit
The 3A @ 200VAC contact rating means each relay can directly switch a small pump contactor coil, a solenoid valve, or an alarm beacon without an interposing relay — but check the inrush of your load; inductive loads like contactor coils need proper snubbing. The SPDT form gives you both NO and NC contacts per output, so you can wire fail-safe logic (pump off on high level) without external relays. The 10kOhm to 40kOhm sensitivity range is the resistance threshold at which the controller detects liquid presence. Set it lower (10kOhm) for low-conductivity liquids like deionized water; set it higher (40kOhm) for conductive fluids like wastewater or caustic solutions. If your probe resistance falls outside this window, the controller won't switch — verify your probe type and liquid conductivity before wiring. Operating temperature range of -10°C to 55°C covers most indoor panel environments but not outdoor enclosures in freezing climates without a heater. The 50m sensor distance is the maximum cable length between the controller and the probe electrodes — longer runs risk false triggering from capacitive coupling or voltage drop in the sense circuit.
Lifecycle and sourcing reality
Sourced to order through independent distribution channels. Availability and current pricing are confirmed at quote time against an RFQ. For volume or blanket-order commitments, the mature lifecycle means long-term supply is predictable — no imminent PCN or LTB to watch for.