Skip to main content
Omron 61F-G3H AC100/200 — General Purpose Relays

Omron 61F-G3H AC100/200 Level Controller, High/Low, 100/200V

MPN61F-G3H AC100/200
Active

Omron 61F series, High/Low Level Controller, 61F-G3H AC100/200, 100/200VAC supply, SPDT relay output, 15kOhm~70kOhm sensitivity, chassis mount, screw terminal.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

61F-G3H AC100/200 — Identification
ParameterValue
Series61F
61F-G3H AC100/200 — Contacts & Switching
ParameterValue
Contact formSPDT (2 Form C)
Contact rating at voltage5A @ 220VAC
61F-G3H AC100/200 — Coil & Supply
ParameterValue
Supply voltage range100/200VAC
61F-G3H AC100/200 — Function & Indication
ParameterValue
TypeHigh/Low Level
61F-G3H AC100/200 — Mechanical
ParameterValue
Mounting typeChassis Mount
Termination styleScrew Terminal
61F-G3H AC100/200 — Environmental
ParameterValue
Operating temperature range-10°C~55°C
61F-G3H AC100/200 — Other specifications
ParameterValue
Weight2.1 lbs (952.5 g)
FeaturesAlarm High/Low - Contact
Output signalRelay (3)
Sensitivity15kOhm ~ 70kOhm
Distance - control to sensor50m

Product details

The Omron 61F-G3H AC100/200 is a conductive level controller from the 61F series, configured as a High/Low type with alarm outputs. It operates on a 100/200VAC supply and provides three relay outputs in an SPDT (2 Form C) contact arrangement, rated at 5A @ 220VAC. The sensitivity adjustment spans 15kOhm to 70kOhm, and the control unit can be mounted up to 50 meters from the sensing electrodes.

The 15kOhm to 70kOhm sensitivity range determines the conductivity threshold at which the relay switches — useful for differentiating between liquids (e.g., water vs. oil) or detecting foam layers. The 50m maximum distance between controller and sensor gives flexibility for tank-side mounting away from the vessel. The SPDT (2 Form C) contacts allow independent high and low alarm circuits plus a common, simplifying panel wiring for pump control or overflow prevention.

Frequently asked questions

What is the sensitivity range of the 61F-G3H AC100/200?

The sensitivity is adjustable from 15kOhm to 70kOhm, allowing the controller to be tuned for different liquid conductivities.

Where can I buy the 61F-G3H AC100/200?

We source this part to order against an RFQ through our independent distribution network. Availability and current pricing are confirmed at quote time.

MPN
61F-G3H AC100/200