Skip to main content
Omron 61F-G4H AC110/120 — General Purpose Relays

Omron 61F-G4H AC110/120 Level Controller, High/Low Level, 11

MPN61F-G4H AC110/120
Active

Omron 61F Series, High/Low Level Controller, 61F-G4H AC110/120, 110/120VAC, 6 Relay Outputs, 15kOhm~70kOhm Sensitivity, Chassis Mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

61F-G4H AC110/120 — Identification
ParameterValue
Series61F
61F-G4H AC110/120 — Contacts & Switching
ParameterValue
Contact formSPDT (2 Form C), SPDT (3 Form C)
Contact rating at voltage5A @ 220VAC
61F-G4H AC110/120 — Coil & Supply
ParameterValue
Supply voltage range110/120VAC
61F-G4H AC110/120 — Function & Indication
ParameterValue
TypeHigh/Low Level
61F-G4H AC110/120 — Mechanical
ParameterValue
Mounting typeChassis Mount
Termination styleScrew Terminal
61F-G4H AC110/120 — Environmental
ParameterValue
Operating temperature range-10°C~55°C
61F-G4H AC110/120 — Other specifications
ParameterValue
Weight3.8 lbs (1.7 kg)
FeaturesIdling Prevention, Level Indication
Output signalRelay (6)
Sensitivity15kOhm ~ 70kOhm
Distance - control to sensor50m

Product details

The Omron 61F-G4H AC110/120 is a conductive level controller from the 61F series, classified as a High/Low Level type. It operates on a 110/120VAC supply and is designed for chassis-mount installation in control panels, typically wired via screw terminals to electrode sensors in tanks or sumps. Six relay outputs handle the switching: SPDT (2 Form C) and SPDT (3 Form C) configurations, rated at 5A @ 220VAC. That means it can directly drive pump contactors or alarm indicators without an interposing relay for most fractional-horsepower loads. The sensitivity adjustment spans 15kOhm to 70kOhm, which sets the threshold for detecting conductive liquid presence through the electrode probe. A lower setting (15kOhm) works for high-conductivity fluids like saltwater; a higher setting (70kOhm) handles low-conductivity media like deionized water or condensate. Maximum distance from the controller to the sensor is 50m, which covers most tank-farm layouts without needing a remote amplifier.

The 15kOhm to 70kOhm sensitivity range is the key selection parameter for this class. If your process fluid has a resistivity outside that window — say, ultrapure water above 1 MOhm-cm — the controller may not reliably detect the level. For most industrial water, wastewater, and chemical solutions, this range covers the typical conductivity band. Six relay outputs give you headroom for multi-point control: fill, drain, high alarm, low alarm, and two spare contacts for annunciation or interlocking. The SPDT form C contacts allow both N.O. and N.C. wiring from the same relay, simplifying fail-safe logic.

Frequently asked questions

Where can I buy the 61F-G4H AC110/120?

This part is sourced and quoted to order against an RFQ through our independent distribution network. Availability and current pricing are confirmed at quote time.

What is the sensitivity range of the 61F-G4H AC110/120?

The sensitivity is adjustable from 15kOhm to 70kOhm, which determines the conductivity threshold for detecting liquid level through the electrode probe.

What is the maximum distance between the controller and the sensor?

The maximum control-to-sensor distance is 50 meters, which covers most tank-farm layouts without requiring a remote amplifier.

MPN
61F-G4H AC110/120