What you're sourcing
The E2EX10MY22MOMS: M18 non-flush brass barrel, 10 mm sensing distance on ferrous targets. NC output — normally closed when the target is absent, opens on detection. Operates across 20–264 VAC/DC, switches up to 300 mA directly. 2 m PVC cable, IP67 rated for wet washdown or dust. Switching frequency is 25 Hz, so this handles moderate-speed detection, not high-speed counting.
Plan B: the NO version
Need the normally-open version? That's E2EX10MY12MOMS — built on the same brass M18 barrel, same 10 mm non-flush sensing range, same cable, same voltage and current ratings. The only difference: output logic is inverted. If your panel was wired expecting a NO sensor, this NC unit will trigger the opposite state. You'll need to either swap the load or invert the logic in the PLC input. Mechanical fit is identical; rewiring is a few minutes with a screwdriver, but a logic flip might be faster.