Omron E5CC-CQ3A5M-001 — Process / Temperature Controllers

Omron E5CC-CQ3A5M-001 Process Controller, PID, 100-240VAC

MPNE5CC-CQ3A5M-001
Active

Omron E5CC-CQ3A5M-001, Process / Temperature Controller, RTD & thermocouple inputs, PID control, analog + 3 relay + SSR outputs, 100-240 VAC, IP66, 45 mm panel cutout.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

E5CC-CQ3A5M-001 — Identification
ParameterValue
SeriesE5CC
TypeProcess, Temperature Controller (RTD, Type B, E, J, K, L, N, PLII, R, S, T, U, W)
E5CC-CQ3A5M-001 — Electrical
ParameterValue
Supply voltage100 ~ 240VAC
E5CC-CQ3A5M-001 — Performance
ParameterValue
Control methodOn/Off, Proportional (PID)
FeaturesEvent Input, Heater Fault Detection
E5CC-CQ3A5M-001 — I/O
ParameterValue
Input range-200°C ~ 2300°C, 0 ~ 20mA, 0 ~ 10VDC
Output typeAnalog, Relay (3), Voltage (External SSR)
E5CC-CQ3A5M-001 — Display
ParameterValue
Display typeLCD - Dual Color Characters, Backlight
Characters per row4, 4
Character height0.600" (15.20mm), 0.280" (7.10mm)
E5CC-CQ3A5M-001 — Environmental
ParameterValue
Operating temperature-10°C ~ 55°C
Ingress protection (IP rating)IP66 - Dust Tight, Water Resistant
E5CC-CQ3A5M-001 — Mechanical
ParameterValue
Mounting typePanel Mount
Panel cutout dimensionsSquare - 45.00mm x 45.00mm
Termination styleScrew Terminal
E5CC-CQ3A5M-001 — Other specifications
ParameterValue
Weight0.265 lb (120.2 g)

Product details

Active production — what that means for your BOM line

The E5CC-CQ3A5M-001: It accepts RTD and thermocouple types B, E, J, K, L, N, PLII, R, S, T, U, W, plus linear 0–20 mA or 0–10 VDC signals, covering just about any process sensor you'd hang off a panel.

Output mix — analog, relays, and SSR drive

Three relay outputs handle on/off or alarm duties, a voltage pulse for an external SSR gives you solid-state switching for heaters, and the analog output can feed a recorder or a remote setpoint — all in one 45 mm square hole. The heater fault detection input (CT) lets the controller monitor current draw and flag a blown heater element, which saves a maintenance walk when you're running a multi-zone oven or extruder.

Panel fit and sealing

Panel cutout is a standard 45 mm square — same as every E5CC, so it drops into existing punch-outs without rework. Screw terminals on the back, no special tooling needed. IP66 rating on the front face means it takes washdown spray and dust — good for food processing or anywhere the panel gets hosed off. The gasket is the seal; don't lose it during install.

Sourcing and documentation

Active and sourced to order against your BOM quantity. Omron provides the standard compliance package: RoHS, REACH, and CE/UL markings are part of the E5CC series datasheet. No special documentation request needed for routine builds.

Frequently asked questions

What is the difference between E5CC-CQ3A5M-001 and E5CC-QX3A5M-001?

Both share the same thermocouple/RTD input range, supply voltage, and panel cutout. The E5CC-CQ3A5M-001 adds an analog output (for recorder or remote setpoint) that the QX3A5M-001 lacks — otherwise the output complement is the same: three relays plus an SSR drive pulse.

Will E5CC-CQ3A5M-001 drop into a panel cut for E5CC-QX2ASM-801?

Yes — both use the same 45 mm square cutout and screw terminals. The wiring is identical for the power and sensor inputs; the output wiring differs only if you use the analog output on the CQ3A5M-001, which the QX2ASM-801 doesn't have.