Skip to main content
Omron E5CC-CX3A5M-000 — Process / Temperature Controllers

Omron E5CC-CX3A5M-000 1/16 DIN Controller, PID

MPNE5CC-CX3A5M-000
Active

Omron E5CC series, 1/16 DIN Process/Temperature Controller, PID with 3 relay and analog outputs, 100-240 VAC, panel mount, IP66.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

E5CC-CX3A5M-000 — Identification
ParameterValue
SeriesE5CC
TypeProcess, Temperature Controller (RTD, Type B, E, J, K, L, N, PLII, R, S, T, U, W)
E5CC-CX3A5M-000 — Electrical
ParameterValue
Supply voltage100 ~ 240VAC
E5CC-CX3A5M-000 — Performance
ParameterValue
Control methodOn/Off, Proportional (PID)
E5CC-CX3A5M-000 — I/O
ParameterValue
Input range-200°C ~ 2300°C, 0 ~ 20mA, 0 ~ 10VDC
Output typeAnalog, Relay (3)
E5CC-CX3A5M-000 — Display
ParameterValue
Display typeLCD - Dual Color Characters, Backlight
Characters per row4, 4
Character height0.600" (15.20mm), 0.280" (7.10mm)
E5CC-CX3A5M-000 — Environmental
ParameterValue
Operating temperature-10°C ~ 55°C
Ingress protection (IP rating)IP66 - Dust Tight, Water Resistant
E5CC-CX3A5M-000 — Mechanical
ParameterValue
Mounting typePanel Mount
Panel cutout dimensionsSquare - 45.00mm x 45.00mm
Termination styleScrew Terminal
E5CC-CX3A5M-000 — Other specifications
ParameterValue
Weight0.265 lb (120.2 g)

Product details

Control and outputs

The E5CC-CX3A5M-000: PID or on/off control, with an analog output for retransmission or a secondary control loop plus three relays for alarms, heater break, or staging. The screw terminals are common to the E5CC family, so panel wiring matches other variants. Keep the analog loop shield tied to panel ground at the controller end to avoid coupling from the relay switching transients.

E5CC-CX3A5M-004 shares the same cutout, terminal layout, and supply voltage but adds an event input and RS-485 (CompoWay/F or Modbus). That costs you an event input and serial communication in exchange for the analog output here. E5CC-RX3A5M-003 drops the analog output and event input for four relays and heater fault detection. If your BOM needs analog retransmission or a second control output, this -000 variant is the only one in the E5CC family that carries it.

Active lifecycle, no last-time-buy notice on file. The E5CC series has been a staple for years, so the next PCN (if one ever comes) will have a long phase-out window. For now, it's a standard quoted-to-order line item.

Frequently asked questions

What is the closest second-source if I can't get this exact code?

E5CC-CX3A5M-004 uses the same mounting and wiring, but adds event input and RS-485 communications while removing the analog output.

What are the key ratings?

Input range covers -200 to 2300°C for thermocouples, plus 0-20 mA and 0-10 VDC. Outputs: one analog and three relays. Front panel is IP66. Supply is 100-240 VAC.

Can E5CC-CX3A5M-004 drop into a panel designed for this controller?

Yes, same cutout, panel thickness, and termination scheme. The only differences are on the function side: event input and RS-485 versus the analog output.

MPN