Skip to main content
Omron E5CC-RW2AUM-800 — Process / Temperature Controllers

Omron E5CC-RW2AUM-800 1/16 DIN PID Controller, 100~240VAC

MPNE5CC-RW2AUM-800
Active

Omron E5CC series 1/16 DIN digital temperature controller, E5CC-RW2AUM-800, 100~240 VAC supply, 3 relay outputs, LCD dual-color display, IP66 front panel, panel mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

E5CC-RW2AUM-800 — Identification
ParameterValue
SeriesE5CC
TypeProcess, Temperature Controller (RTD, Type B, E, J, K, L, N, PLII, R, S, T, U, W)
E5CC-RW2AUM-800 — Electrical
ParameterValue
Supply voltage100 ~ 240VAC
E5CC-RW2AUM-800 — Performance
ParameterValue
Control methodOn/Off, Proportional (PID)
E5CC-RW2AUM-800 — I/O
ParameterValue
Input range-200°C ~ 2300°C, 0 ~ 20mA, 0 ~ 10VDC
Output typeRelay (3)
E5CC-RW2AUM-800 — Display
ParameterValue
Display typeLCD - Dual Color Characters, Backlight
Characters per row4, 4
Character height0.600" (15.20mm), 0.280" (7.10mm)
E5CC-RW2AUM-800 — Environmental
ParameterValue
Operating temperature-10°C ~ 55°C
Ingress protection (IP rating)IP66 - Dust Tight, Water Resistant
E5CC-RW2AUM-800 — Mechanical
ParameterValue
Mounting typePanel Mount
Panel cutout dimensionsSquare - 45.00mm x 45.00mm
Termination stylePlug In, 11 Pin (Octal)
E5CC-RW2AUM-800 — Other specifications
ParameterValue
Weight0.265 lb (120.2 g)

Product details

Panel integration and duty

The E5CC-RW2AUM-800 is a 1/16 DIN PID controller that fits a 45mm square panel cutout, standard for retrofit or new panel builds. The IP66 front rating means the face holds up to washdown in food or chemical lines — the seal is at the bezel, not just the display window.

Input flexibility and output count

Accepts RTD and 13 thermocouple types (B, E, J, K, L, N, PLII, R, S, T, U, W) plus 0–20 mA or 0–10 VDC linear inputs — covers most process sensors without an external signal conditioner. The three relay outputs handle on/off or PID control for heaters, solenoid valves, or alarm circuits.

Supply voltage and sibling comparison

Runs on 100~240 VAC, which is the main difference from the E5CC-RW2DUM-000 (24 VAC/DC). If your panel already has a 24 V supply, that sibling saves a transformer; for line-voltage panels this unit drops straight in. Both share the same 3-relay output set and IP66 front.

Frequently asked questions

How can I order the E5CC-RW2AUM-800 and get a price?

Quoted to order against your BOM quantity through independent distribution.

What is the difference between the E5CC-RW2AUM-800 and other E5CC models?

The main difference is supply voltage: this unit is 100~240 VAC, while the E5CC-RW2DUM-000 is 24 VAC/DC. Both have 3 relay outputs and the same IP66 front. Models like the E5CC-QX2ASM-801 swap one relay for a voltage output to drive an external SSR, and add heater fault detection.

MPN
E5CC-RW2AUM-800