Omron E5CC-RX3A5M-5803U

Omron E5CC-RX3A5M-5803U Process/Temp Controller, PID, RS-485

MPN E5CC-RX3A5M-5803U
Active

Omron E5CC-RX3A5M-5803U process/temperature controller, PID control, RTD/TC/mA/V inputs, 4 relay outputs, RS-485 CompoWay/F Modbus, IP66 front, 100-240 VAC.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

E5CC-RX3A5M-5803U specifications
ParameterValue
SeriesE5CC
Output signalRelay (4)
Supply voltage100 to 240VAC
IP ratingIP66
ProtocolRS-485 (CompoWay/F, Modbus)
MountingPanel Mount
Temp operating max55 °C
Temp operating min-10 °C
Weight0.265 lb (120.2 g)
PackageBulk
Control methodOn/Off, Proportional (PID)

Product details

Active production — what that means for your BOM

The E5CC-RX3A5M-5803U: The part is quoted to order against your BOM quantity; lead time and volume pricing are confirmed at RFQ.

Input flexibility and control loop

The controller accepts RTD, thermocouple types B/E/J/K/L/N/PLII/R/S/T/U/W, plus 0–20 mA and 0–10 VDC process signals, covering the full range from -200°C to 2300°C. That means one part number handles both temperature and analog process loops — no separate model for mA vs TC inputs. Control method is On/Off or full PID, so you can tune it for aggressive ramp-and-soak profiles or simple threshold switching without swapping hardware.

Communications and outputs

Four relay outputs give you separate control, alarm, and event channels — enough for a heating/cooling split plus a high/low alarm pair. The RS-485 port speaks both CompoWay/F and Modbus, so it drops into existing PLC networks without a protocol converter. The IP66 front panel rating means the display and keys survive washdown in food or chemical environments — the sealing is at the bezel, not the housing, so the rear terminals remain in the panel's dry side.

Panel cutout and starter kit

The 45.00 mm x 45.00 mm square cutout is the standard 1/16 DIN footprint — no special punch or adapter frame needed. The starter kit includes the controller, cable, and configuration software, so a first-off commissioning doesn't require separate ordering of accessories.

MPN
E5CC-RX3A5M-5803U