Skip to main content
Omron E5DC-CX0ASM-015 — Process / Temperature Controllers

Omron E5DC-CX0ASM-015 Process/Temp Controller, Analog Output

MPNE5DC-CX0ASM-015
Active

Omron E5DC series, Process/Temperature Controller, DIN Rail mount, Analog output, RS-485 (Modbus), 100-240 VAC supply, accepts RTD/TC/mA/V inputs.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

E5DC-CX0ASM-015 — Identification
ParameterValue
SeriesE5DC
TypeProcess, Temperature Controller (RTD, Type B, E, J, K, L, N, PLII, R, S, T, U, W)
E5DC-CX0ASM-015 — Electrical
ParameterValue
Supply voltage100 ~ 240VAC
E5DC-CX0ASM-015 — Performance
ParameterValue
Control methodOn/Off, Proportional (PID)
E5DC-CX0ASM-015 — I/O
ParameterValue
Input range-200°C ~ 2300°C, 0 ~ 20mA, 0 ~ 10VDC
Output typeAnalog
E5DC-CX0ASM-015 — Communication
ParameterValue
Communication interfacesRS-485 (CompoWay/F, Modbus)
E5DC-CX0ASM-015 — Display
ParameterValue
Display typeLCD - Dual Color Characters, Backlight
Characters per row4, 4
Character height0.334" (8.50mm), 0.314" (8.00mm)
E5DC-CX0ASM-015 — Environmental
ParameterValue
Operating temperature-10°C ~ 55°C
Ingress protection (IP rating)IP20
E5DC-CX0ASM-015 — Mechanical
ParameterValue
Mounting typeDIN Rail
Termination styleScrew Terminal
E5DC-CX0ASM-015 — Other specifications
ParameterValue
Weight0.265 lb (120.2 g)

Product details

DIN-rail PID with analog output and Modbus

The Omron E5DC-CX0ASM-015 is a DIN-rail-mount process and temperature controller that accepts RTD and thermocouple types B, E, J, K, L, N, PLII, R, S, T, U, W, plus 0-20 mA and 0-10 VDC linear inputs, covering a span from -200°C to 2300°C. It outputs a linear analog signal rather than relay or SSR-drive pulses, making it the pick when the downstream device — a valve positioner, a SCR power controller, or a chart recorder — expects a 4-20 mA or 0-10 VDC setpoint. On/Off or PID control method is selectable per loop, and the RS-485 port (CompoWay/F or Modbus) lets a PLC or SCADA read the PV, write the SP, and tune the PID terms without opening the panel door.

Panel fit and supply wiring

Screw-terminal termination on a DIN-rail body means it clips into the same 35 mm rail as the rest of the panel controls — no panel cutout, no bezel, no NEMA 4X hole to punch. Rated for 100-240 VAC supply, so it runs directly off the panel control transformer without a separate 24 VDC power supply; the dual-color LCD backlight shows PV and SP on two 4-character rows readable at a glance. IP20 rating means it belongs inside a clean, dry enclosure — not on the machine frame exposed to washdown or dust.

Active lifecycle and sourcing

Frequently asked questions

Where can I buy the Omron E5DC-CX0ASM-015 and what is the lead time?

The E5DC-CX0ASM-015 is sourced to order against an RFQ. Availability and current lead time are confirmed at quote time through our independent distribution network — no stock-holding claim, but we quote against the BOM quantity.

Can the E5DC-CX0ASM-015 replace an existing Omron E5DC model with relay outputs?

The E5DC-CX0ASM-015 outputs an analog signal, not relay contacts or SSR-drive voltage. If the existing controller drives a contactor or solid-state relay directly, this unit needs an intermediate signal conditioner or a different E5DC variant with relay/voltage outputs (e.g., the E5DC-QX2DSM-017). The input range, RS-485 protocol, and DIN-rail footprint are shared across the E5DC family.

MPN
E5DC-CX0ASM-015