Omron E5DC-RX2ASM-017 Process / Temperature Controller, DIN Rail, 100-240 VAC, 3 Relay Outputs, PID Control, RTD and Thermocouple Inputs, LCD Display.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

E5DC-RX2ASM-017 — Identification
ParameterValue
SeriesE5DC
TypeProcess, Temperature Controller (RTD, Type B, E, J, K, L, N, PLII, R, S, T, U, W)
E5DC-RX2ASM-017 — Electrical
ParameterValue
Supply voltage100 ~ 240VAC
E5DC-RX2ASM-017 — Performance
ParameterValue
Control methodOn/Off, Proportional (PID)
FeaturesEvent Input, Heater Fault Detection
E5DC-RX2ASM-017 — I/O
ParameterValue
Input range-200°C ~ 2300°C, 0 ~ 20mA, 0 ~ 10VDC
Output typeRelay (3)
E5DC-RX2ASM-017 — Display
ParameterValue
Display typeLCD - Dual Color Characters, Backlight
Characters per row4, 4
Character height0.334" (8.50mm), 0.314" (8.00mm)
E5DC-RX2ASM-017 — Environmental
ParameterValue
Operating temperature-10°C ~ 55°C
Ingress protection (IP rating)IP20
E5DC-RX2ASM-017 — Mechanical
ParameterValue
Mounting typeDIN Rail
Termination styleScrew Terminal
E5DC-RX2ASM-017 — Other specifications
ParameterValue
Weight0.265 lb (120.2 g)

Product details

Controller type and input flexibility

The E5DC-RX2ASM-017 is a DIN-rail-mount process and temperature controller accepting RTD, thermocouple types B, E, J, K, L, N, PLII, R, S, T, U, W, plus 0-20 mA and 0-10 VDC linear signals — one unit covers both temperature loops and analog process variables without a separate signal conditioner. Input range spans -200°C to 2300°C for thermocouples, matching furnace, oven, and extruder profiles; the 0-20 mA and 0-10 VDC ranges handle pressure, flow, or level transmitters in the same slot.

Outputs and control logic for multi-zone loops

Three relay outputs let the controller drive a contactor for heating, a second for cooling, and a third for alarm or event-triggered shutdown — no external interposing relay needed for the third function. Heater fault detection monitors current draw on the load side and flags a broken heater element before the process drifts. Control method is selectable between on/off and proportional (PID) with auto-tune — the PID loop handles thermal lag in ovens and baths without overshoot at setpoint.

Panel fit and supply voltage

Universal 100-240 VAC supply means the same part number works on 110 V or 220 V line feeds without a voltage selector or external transformer — simplifies spares stocking for plants with mixed line voltages.

Frequently asked questions

What is the difference between E5DC-RX2ASM-017 and E5DC-QX2DSM-017?

The E5DC-RX2ASM-017 runs on 100-240 VAC and has three relay outputs. The E5DC-QX2DSM-017 runs on 24 VAC/DC and has two relays plus a voltage (SSR drive) output — so if your panel has a 24 V control bus and you need to drive an external SSR, the QX2DSM variant is the fit. Both share the same DIN-rail footprint, screw terminals, input range, and IP20 rating.

How do I order the E5DC-RX2ASM-017 and get a price?

The E5DC-RX2ASM-017 is quoted to order against your BOM quantity.

MPN
E5DC-RX2ASM-017