Skip to main content
Omron E5EC-QX2DBM-011 — Process / Temperature Controllers

Omron E5EC-QX2DBM-011 Temperature Controller, PID, 24VAC/DC

MPNE5EC-QX2DBM-011
Active

Omron E5EC series temperature controller, E5EC-QX2DBM-011, universal RTD/thermocouple input range -200°C to 2300°C, relay (3) and voltage (2) outputs, 24VAC/DC supply, PID control, IP66 front panel.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

E5EC-QX2DBM-011 — Identification
ParameterValue
SeriesE5EC
TypeTemperature Controller (RTD, Type B, E, J, K, L, N, PLII, R, S, T, U, W)
E5EC-QX2DBM-011 — Electrical
ParameterValue
Supply voltage24VAC/DC
E5EC-QX2DBM-011 — Performance
ParameterValue
Control methodOn/Off, Proportional (PID)
FeaturesHeater Fault Detection
E5EC-QX2DBM-011 — I/O
ParameterValue
Input range-200°C ~ 2300°C, 0 ~ 20mA, 0 ~ 10VDC
Output typeRelay (3), Voltage (External SSR) (2)
E5EC-QX2DBM-011 — Display
ParameterValue
Display typeLCD - Tri Color Characters, Backlight
Characters per row4, 4, 4
Character height0.710" (18.00mm), 0.433" (11.00mm), 0.307" (7.80mm)
E5EC-QX2DBM-011 — Environmental
ParameterValue
Operating temperature-10°C ~ 55°C
Ingress protection (IP rating)IP66 - Dust Tight, Water Resistant
E5EC-QX2DBM-011 — Mechanical
ParameterValue
Mounting typePanel Mount
Panel cutout dimensionsRectangular - 92.00mm x 45.00mm
Termination styleSpring Terminal
E5EC-QX2DBM-011 — Other specifications
ParameterValue
Weight0.463 lb (210.01 g)

Product details

What it fits — the E5EC-QX2DBM-011 in a panel

The E5EC-QX2DBM-011 is a 1/16 DIN-size temperature controller from Omron's E5EC series. It accepts a wide range of sensor inputs — RTD and thermocouple types B, E, J, K, L, N, PLII, R, S, T, U, W — covering the full spread from cryogenic to furnace work. The input range spans -200°C to 2300°C, plus linear 0–20 mA and 0–10 VDC signals, so it handles most process loops without a signal conditioner. Control method is On/Off or full PID — the PID loop auto-tunes on demand, which saves time during commissioning on a new oven or oven zone.

Outputs that matter on a line-down swap

Three relay outputs handle the main load, alarm, or event functions. Two voltage-pulse outputs drive external SSRs directly — no interposing relay needed for the heating element call. Heater fault detection is built in. It monitors the load current through a separate CT input and flags a broken heater or SSR short before the process drifts. That feature alone can save a production batch on a temperature-critical line. Compared to the E5EC-RX2DBM-010 (four relay outputs, no voltage outputs), the QX2DBM-011 trades one relay for two SSR-drive channels — essential if the downstream contactor bank uses DC-switched SSRs.

Panel mount with a 92.00 mm x 45.00 mm rectangular cutout. Spring-terminal connections on the back. The front bezel is rated IP66 — dust-tight and protected against hose-down. That means it can sit on a washdown panel face in a food plant or a wet grinding area without a cover. The tri-color LCD backlight shows four characters per row across three rows — process value, setpoint, and status in one glance.

Frequently asked questions

Where can I buy the Omron E5EC-QX2DBM-011 and get a price?

The E5EC-QX2DBM-011 is sourced to order against an RFQ through independent distribution.

What is the difference between E5EC-QX2DBM-011 and E5EC-RX2DBM-010?

The QX2DBM-011 has three relay outputs plus two voltage-pulse outputs for external SSRs. The RX2DBM-010 has four relay outputs and no voltage outputs — choose the QX2 if your load circuit uses DC-switched SSRs, the RX2 if you need four discrete relay channels.

Does E5EC-QX2DBM-011 support heater fault detection?

Yes, heater fault detection is a built-in feature. It monitors load current via an external CT and flags broken heaters or shorted SSRs.

MPN
E5EC-QX2DBM-011