What the 6 A rating means for fit
The G2RV-SL500 DC12: The 6 A contact rating is the continuous resistive current the relay can switch without derating. For motor or inductive loads, apply the standard AC-15 / DC-13 derating curve — the 6 A figure is not a catch-all. In a control panel, this relay typically handles solenoid valves, contactor coils, or indicator lamps; verify the inrush current of the load stays within the make/break capacity of the contact set.