Skip to main content
Omron G3PE-235B-2N — Solid State Relays

Omron G3PE-235B-2N 3-Phase SSR, 35A, 100-240 VAC

MPNG3PE-235B-2N

Omron G3PE series 3-phase solid state relay, G3PE-235B-2N, 35 A load current at 40°C, 100-240 VAC output, 12-24 VDC input, zero-cross switching, screw terminals.

$262.00Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

G3PE-235B-2N key specifications
ParameterValue
Product type3-phase Heater Control
Voltage12 to 24 VDC
Operate voltage9.6 VDC max.
Release voltage1 VDC min.
Load voltage range75 to 264 VAC
Rated load voltage100 to 240 VAC
Operating voltage range9.6 to 30 VDC
Load current35 A (at 40 ?)
Input current10 mA max. (at 24 VDC)
Minimum load current0.5 A
Inrush current resistivity440 A (60 Hz 1 cycle)
Applicable loadLoad carrying capacity - 12.1 kW (at 200 VAC)

All specifications

G3PE-235B-2N additional specifications
ParameterValue
Terminal structureScrew terminal
Weight3 Kg
InputRated voltage : 12 to 24 VDCOperating voltage range : 9.6 to 30 VDCInput current : 10 mA max. (at 24 VDC)Operate voltage : 9.6 VDC max.Release voltage : 1 VDC min.
OutputRated load voltage : 100 to 240 VACLoad voltage range : 75 to 264 VACMinimum load current : 0.5 ALoad current : 35 A (at 40 ?)Inrush current resistivity : 440 A (60 Hz 1 cycle)Permissible I2**t : 1260 A2sApplicable load : Load carrying capacity - 12.1 kW (at 200 VAC)
Isolation methodPhototriac
Permissible i2**t1260 A2s
Estimated lead time1 - 10 working days.
Zero cross functionEquipped

Product details

The Omron G3PE-235B-2N is a 3-phase solid state relay (SSR) purpose-built for heater control — resistive loads only, no inductive or motor switching. It switches 35 A per phase at up to 240 VAC, driven by a 12-24 VDC control signal. Rated load voltage is 100 to 240 VAC (operating range 75 to 264 VAC), so it covers standard 200/208/240 VAC three-phase heater circuits common in industrial ovens, packaging seal bars, and injection-molding barrel heaters. The 35 A load current rating (at 40°C ambient) is the continuous current per phase. For a 200 VAC line, that translates to roughly 12.1 kW of heater load — enough for a medium-sized industrial oven zone.

Control input and switching behaviour

The DC control input accepts 12-24 VDC (operating range 9.6 to 30 VDC) and draws 10 mA max at 24 VDC. The release voltage is 1 VDC min, so the SSR drops out cleanly on a low signal — important for fail-safe heater cut-off in safety circuits. Zero-cross function is equipped, meaning the output turns on only at the AC voltage zero crossing. This reduces inrush current and electrical noise — critical for heater life and for keeping switching transients off the line feeding sensitive PLC or drive loads. Phototriac isolation separates the control side from the power side, providing galvanic isolation — no direct electrical path between the 24 VDC control and the 240 VAC heater circuit.

Submit an RFQ for firm delivery and pricing.

Integration notes

Minimum load current is 0.5 A — below that, the SSR may not switch reliably. If your heater element draws less than 0.5 A (e.g. a small cartridge heater), add a dummy load or select a different SSR. Inrush current resistivity is 440 A for 1 cycle at 60 Hz, and permissible I²t is 1260 A²s. This means the SSR can handle cold-start heater inrush without welding the output triac — a common failure mode in heater SSRs.

Frequently asked questions

What is the lead time for the G3PE-235B-2N?

Typical lead time is 1-10 working days. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm delivery date.

What is the closest alternative to the G3PE-235B-2N in the same family?

Within the G3PE series, the closest alternative would be a different current rating (e.g., 25 A or 45 A) or a different control voltage variant. No pin-compatible direct substitute is listed; confirm the load current and control voltage requirements before selecting an alternative.

What are the input specifications for the G3PE-235B-2N?

The DC control input is rated 12-24 VDC, operating range 9.6-30 VDC, drawing 10 mA max at 24 VDC. Operate voltage is 9.6 VDC max, release voltage is 1 VDC min.

What are the output specifications for the G3PE-235B-2N?

Rated load voltage is 100-240 VAC (operating range 75-264 VAC). Load current is 35 A at 40°C, minimum load current 0.5 A. Inrush current resistivity is 440 A (60 Hz 1 cycle), permissible I²t is 1260 A²s. Applicable load is 12.1 kW at 200 VAC.

MPN
G3PE-235B-2N