The NXRS1201: The module fits a 12 mm DIN-rail footprint with a removable screwless push-in terminal block (16 terminals). Conversion cycle runs at 125 µs per sample, configurable for free-running, synchronous, or task-period-prioritized refresh.
24-bit resolution on a ±5 mV/V input range. The differential input circuit rejects common-mode noise from long cable runs; with a ±0.1 µV/°C RTI zero drift, long-term stability holds without frequent tare recalibration.
Integration note
Mounts on a DIN rail; width 12 mm leaves room for adjacent NX slices. The removable screwless terminal block has 16 terminals and pulls out without depopulating the rail. Requires an NX-PF power supply unit on the bus; the module itself draws backplane power only (no external 24 V needed). IP20 enclosure suits clean indoor panels. After mounting, allow a 30-minute warm-up before taking critical readings; the rated drift specifications assume thermal equilibrium.