S8FSG15024CD key specifications
ParameterValue
SeriesS8FS- G
Wire connection typeScrew Terminals
Input voltage100 to 240V AC
Output voltage - nominal24 V DC
Current - inrush28 A
Output current6.5 A
Power supply styleSwitching
Output power - rated150 W
Input frequency - minimum47 Hz
Input frequency - nominal50/60 Hz
Input frequency - maximuim450 Hz
PhasesSingle

All specifications

S8FSG15024CD additional specifications
ParameterValue
MountingDIN Rail
Wire size - maximum12 AWG
Wire size - minimum16 AWG
Operating temperature - maximum158 °F
Operating temperature - minimum-4 °F
Overall depth7.76 in
Overall width1.74 in
Overall height3.82 in
Housing materialAluminum; Stainless Steel
Mean time between failures135,000 hr
StandardscUL; cUR; SEMI F47-0706 (200 VAC input); UL 508 (Listing); UL: UL 60950-1 (Recognition); VDE
Special featuresAutomatic Reset; LED Diagnostic Indicators; Overload Protection; Overvoltage Protection; Series Operation
Status indicatorGreen LED
Hold up time - minimum10 msec; 55 msec
Output noise - maximum110 mV
Start up time - maximum1,000 msec
Maximum efficiency @ 230V AC90 %

Product details

The Omron S8FSG15024CD is a 150 W DIN-rail switching power supply delivering 24 V DC at 6.5 A from a single-phase 100-240 V AC input. The 90% efficiency at 230 V AC keeps heat dissipation low in a crowded enclosure.

Rated 150 W continuous at 6.5 A output, 24 V DC nominal — enough to power a small control cabinet's 24 VDC loads: a handful of contactors, a compact PLC, and a few sensors. The single-phase input accepts 100-240 V AC at 47-450 Hz, which covers standard mains (50/60 Hz) and higher-frequency supplies found in some industrial settings. Inrush current is limited to 28 A, so it won't nuisance-trip a B-curve MCB on power-up. Hold-up time is a minimum of 10 msec (55 msec typical) at full load — enough to ride through a half-cycle dropout and keep a PLC from cycling its outputs. Output noise is spec'd at 110 mV max, which is within tolerance for most digital I/O and analog inputs; if you're feeding a sensitive measurement chain, add a small output filter cap at the load. Built-in protections include overload, overvoltage, and automatic reset — meaning it recovers from a temporary overload without a manual reset, which saves a truck roll on a remote panel. The green LED gives a quick visual confirmation the rail is alive.

Frequently asked questions

What compliance documentation does Omron provide for S8FSG15024CD?

The unit carries cUL, cUR, UL 508 listing, UL 60950-1 recognition, SEMI F47-0706 (at 200 VAC input), and VDE approvals. RoHS and REACH declarations are standard from Omron for this series.

MPN