S8VK-T24024 key specifications
ParameterValue
SeriesS8VK-T
Voltage_in400 VAC
Voltage out24 V DC
Voltage in max576 V
Voltage in min320 V
Current out10 A
Frequency min47 Hz
PhasesThree
MountingDIN Rail
Terminal_typeRod Terminals
Temp operating max158 °F
Temp operating min-40 °F

All specifications

S8VK-T24024 additional specifications
ParameterValue
Depth150.114
Width59.944
Height124.968
Mtbf_hours135000 h
Mean_time_between_failures_mtbf135000 hr
StandardsEN/IEC 60529
PowerSwitching
Size max10 AWG
Size min22 AWG
IP ratingIP20
Power_out240 W
Output signalAdjustable
I/O channels1
Ripple noise0.19 V
Frequency63
Product typePower Supply
Efficiency89
Input voltage480
Switching current29
Has_status_indicatorGreen LED
Insulation voltage3000
Output current max10
Special_features_textLED Diagnostic Indicators; Overload Protection; Overvoltage Protection; Parallel Capability; Series Operation
Hold up time - minimum min24 msec
Output noise - maximum max50 mV
Start up time - maximum max600 msec

Product details

What this power supply gives you

The Omron S8VK-T24024 is a three-phase DIN rail power supply delivering 240 W at 24 V DC, with an adjustable output and full load current of 10 A. It accepts a wide three-phase input range of 320 to 576 V AC (47-63 Hz), making it a standard fit for 400 V industrial panels. Efficiency hits 89%, and the MTBF is rated at 135000 hours — a solid number for a critical line-side spare. The output is adjustable (within the 24 V range), and ripple noise is 0.19 V, clean enough for most PLC and sensor loads. Hold-up time is a minimum 24 msec, enough to ride through a half-cycle dip. Startup time max is 600 msec.

Mounting and termination

Rod terminals accept 22 AWG to 10 AWG; depth 150.114 mm, width 59.944 mm, height 124.968 mm. IP20 rated.

Environmental and protection

Operating temperature covers -40 °F to 158 °F; standard protections include overload, overvoltage, and parallel/series operation capability, and a green LED indicates output status. Insulation voltage tested at 3000 V.

Frequently asked questions

What is the difference between S8VK-T24024 and S8VKT24024?

No functional difference. S8VKT24024 is an alternate code for the same unit. Either order code will source the identical three-phase 240W 24V power supply.

What is its phase configuration?

Three-phase input (320–576 V AC 47–63 Hz). It is designed for 400 V industrial mains.

Will it drop into a panel specified for S8VKT24024?

Yes. The specs are identical — same dimensions, same terminals, same ratings. No rewiring needed.

MPN