Skip to main content
Schneider Electric 140DAI35300C

Schneider Electric 140DAI35300C

MPN140DAI35300C
Obsolete

Discrete Input Module

$1,544.32 – $2,642.00Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

140DAI35300C key specifications
ParameterValue
Range of productModicon Quantum automation platform
Product or component typeVAC discrete input modules
Discrete input voltage24 V AC
Voltage state 0 guaranteed0...5 V 57...63 Hz 0...5 V 47...53 Hz
Voltage state 1 guaranteed12...30 V AC 57...63 Hz 14...30 V AC 47...53 Hz
Input current11.1 mA 57...63 Hz 13.2 mA 47...53 Hz
Bus current requirement250 mA
Maximum leakage current1.9 mA
Maximum power dissipation in10.9 W
Network frequency limits47...63 Hz
Response time4.9...0.75 ms x line cycle Off-On 7.3...12.3 ms On-Off
Relative humidity95 % without condensation

All specifications

140DAI35300C additional specifications
ParameterValue
Operating altitude<= 16404.2 ft (5000 m)
StandardsCSA C22.2 No 142 UL 508
MarkingCE
Category18155-QUANTUM I/O & POWER SUPPLIES
Module formatStandard
Software nameProWORX 32 Unity Pro Concept
Input impedance2600 Ohm capacitive 57...63 Hz 3100 Ohm capacitive 47...53 Hz
Local signalling1 LED (green) for bus communication is present (Active) 1 LED (red) for external fault detected (F) 32 LEDs (green) for input status
Group of channels4
Protective treatmentConformal coating Humiseal 1A33
Discrete input number32
Absolute maximum input30 V continuous 32 V 10 s 50 V 1 cycle
Addressing requirement2 input words
Isolation between group1780 Vrms for 1 minute
Isolation between group and bus1780 Vrms for 1 minute
Ambient air temperature for storage-40...185 °F (-40...85 °C)
Resistance to electromagnetic fields9.1 V/m (10 V/m) 80...2000 MHz IEC 801-3
Ambient air temperature for operation32...140 °F (0...60 °C)
Resistance to electrostatic discharge4 kV contact IEC 801-2 8 kV on air IEC 801-2
MPN
140DAI35300C