Schneider 140DDI36400C Discrete Input Module
MPN140DDI36400C
End of Life
Discrete Input Module
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →Specifications
| Parameter | Value |
|---|---|
| Range of product | Modicon Quantum automation platform |
| Product or component type | Low voltage dc discrete input modules |
| Input voltage limits | 19.2...30 V |
| Discrete input voltage | 24 V DC |
| Voltage state 0 guaranteed | 5 V DC |
| Voltage state 1 guaranteed | 15...30 V DC |
| Bus current requirement | 270 mA |
| Current state 0 guaranteed | >= 0.7 mA |
| Current state 1 guaranteed | >= 2.5 mA |
| Power dissipation | 1.35 W + (0.13 x number of points on) |
| Response time | <= 3 ms from state 1 to state 0 |
| Relative humidity | 95 % without condensation |
All specifications
| Parameter | Value |
|---|---|
| Operating altitude | <= 16404.2 ft (5000 m) |
| Standards | CSA C22.2 No 142 UL 508 |
| Marking | CE |
| Category | US1PC2118155 |
| Logic input | Positive (sink) |
| Module format | Standard |
| Input impedance | 6700 Ohm |
| Local signalling | 1 LED (green) for bus communication is present (Active) 1 LED (red) for external fault detected (F) 96 LEDs (green) for input status |
| Group of channels | 6 |
| Protective treatment | Conformal coating Humiseal 1A33 |
| Discrete input number | 96 |
| Absolute maximum input | 30 V continuous 50 V decaying pulse |
| Addressing requirement | 6 words |
| Isolation between group | 500 Vrms for 1 minute |
| Ambient air temperature for storage | -40...185 °F (-40...85 °C) |
| Resistance to electromagnetic fields | 9.1 V/m (10 V/m) 80...2000 MHz IEC 801-3 |
| Ambient air temperature for operation | 32...140 °F (0...60 °C) |
| Resistance to electrostatic discharge | 4 kV contact IEC 801-2 8 kV on air IEC 801-2 |
MPN
140DDI36400C