Specifications

140DVO85300 key specifications
ParameterValue
Protection typeInternal output protection by 5 A fuse per group
Range of productModicon Quantum automation platform
Product or component typeDc discrete output module
Maximum voltage drop<0.4 V 0.5 A
Discrete output voltage10...30 V DC
Surge current2.5 A 1 ms
Maximum load current<= 4 A each group
Bus current requirement500 mA
Short-circuit protectionWith
Power dissipation2.5 W + (0.1 x all points on) + (0.4 x total load current)
Response time1 ms at state 0 to state 1 1 ms at state 1 to state 0
Relative humidity95 % without condensation

All specifications

140DVO85300 additional specifications
ParameterValue
Operating altitude<= 16404.2 ft (5000 m)
StandardsUL 508 CSA C22.2 No 142
MarkingCE
CategoryUS1PC2118155
Module formatStandard
Load inductanceInductance(H) = 0.5/((current(A))² x (switching frequency(Hz))) 0.5...4 Hz
Fault indicationIncorrect output state Loss of field power Blown fuse
Local signalling1 LED (green) for bus communication is present (Active) 1 LED (red) for external fault detected (F) 32 LEDs (green) for input status
Group of channels4 groups of 8
Discrete output logicNegative logic (sink)
Maximum tungsten load2.5 W 10 V 3 W 12 V 6 W 24 V
Addressing requirement2 output words 2 input words
Discrete output number32
Absolute maximum output50 V 1 s decaying pulse
Output overvoltage protectionWith
Ambient air temperature for storage-40...185 °F (-40...85 °C)
Resistance to electromagnetic fields9.1 V/m (10 V/m) 80...2000 MHz IEC 801-3
Ambient air temperature for operation32...140 °F (0...60 °C)
Resistance to electrostatic discharge4 kV contact IEC 801-2 8 kV on air IEC 801-2
MPN