circuit breaker Compact NS100N - TMD - 16 A - 1 pole 1d

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jun 2026

Specifications

29585 — Identification
ParameterValue
Product range (series)Compact NS100...630
Product/component typeCircuit breaker
Device applicationDistribution
29585 — Ratings
ParameterValue
Rated current (In)100 A at 40 °C 100 A at 65 °C
Poles configuration1P
Breaking capacity25 kA at 240 V AC 50/60 Hz conforming to NEMA AB1 HIC 25 kA at 277 V AC 50/60 Hz conforming to NEMA AB1 HIC 25 kA Icu at 220 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 277 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 250 V DC 1P conforming to IEC 60947-2 50 kA Icu at 48/125 V DC 1P conforming to IEC 60947-2
Rated service breaking capacity (Ics)25 kA at 220 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 277 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 250 V DC conforming to IEC 60947-2 50 kA at 48/125 V DC conforming to IEC 60947-2
Rated operational voltage (Ue)250 V DC conforming to IEC 60947-2 277 V AC 50/60 Hz conforming to IEC 60947-2
Rated insulation voltage (Ui)750 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)DC AC
Network frequency50/60 Hz
Utilisation categoryCategory A
29585 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)10000 cycles 277 V AC 50/60 Hz In conforming to IEC 60947-2 20000 cycles 277 V AC 50/60 Hz In/2 conforming to IEC 60947-2
Mechanical durability (cycles)20000 cycles
29585 — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeToggle
Local signalling/indicationPositive contact indication
Width35 mm
Height161 mm
Depth86 mm
29585 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
29585 — Approvals
ParameterValue
StandardsIEC 60947-2
MPN
29585