Skip to main content
Schneider Electric 35934 — Miniature Circuit Breakers (MCB)

Schneider Electric 35934

MPN35934
Active

circuit breaker Compact NS250 SX - TMD - 100 A - 3 poles 3d

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jun 2026

Specifications

35934 — Identification
ParameterValue
Product range (series)Compact NS100...630
Product/component typeCircuit breaker
Device applicationDistribution
35934 — Ratings
ParameterValue
Rated current (In)220 A at 65 °C 250 A at 40 °C
Poles configuration3P
Breaking capacity10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-2
Rated insulation voltage (Ui)750 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
35934 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)10000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2 20000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2
Mechanical durability (cycles)20000 cycles
35934 — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeToggle
Local signalling/indicationPositive contact indication
Width105 mm
Height161 mm
Depth86 mm
35934 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
35934 — Approvals
ParameterValue
StandardsIEC 60947-2
MPN
35934