Skip to main content
Schneider Electric 37649 — Miniature Circuit Breakers (MCB)

Schneider Electric 37649

MPN37649
Active

circuit breaker Compact NSF150N - TMD - 50 A - 3 poles 3d

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jun 2026

Specifications

37649 — Identification
ParameterValue
Product range (series)NSF100...250
Product/component typeCircuit breaker
Device applicationDistribution
37649 — Ratings
ParameterValue
Poles configuration3P
Breaking capacity22 kA Icu 525 V AC 50/60 Hz IEC 60947-2 30 kA Icu 500 V AC 50/60 Hz IEC 60947-2 85 kA Icu 220/240 V AC 50/60 Hz IEC 60947-2 35 kA Icu 440 V AC 50/60 Hz IEC 60947-2 36 kA Icu 380/415 V AC 50/60 Hz IEC 60947-2 50 kA Icu 250 V DC 1P IEC 60947-2 50 kA Icu 500 V DC 2P IEC 60947-2 8 kA Icu 600/690 V AC 50/60 Hz IEC 60947-2
Rated service breaking capacity (Ics)22 kA 525 V AC 50/60 Hz IEC 60947-2 30 kA 500 V AC 50/60 Hz IEC 60947-2 85 kA 220/240 V AC 50/60 Hz IEC 60947-2 35 kA 440 V AC 50/60 Hz IEC 60947-2 36 kA 380/415 V AC 50/60 Hz IEC 60947-2 50 kA 250 V DC IEC 60947-2 50 kA 500 V DC IEC 60947-2 8 kA 600/690 V AC 50/60 Hz IEC 60947-2
Rated operational voltage (Ue)500 V DC IEC 60947-2
Rated insulation voltage (Ui)750 V AC 50/60 Hz IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kVIEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
37649 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Suitability for isolationYes IEC 60947-2
37649 — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeToggle
Local signalling/indicationPositive contact indication
Width4.1 in (105 mm)
Height6.3 in (161 mm)
Depth3.4 in (86 mm)
37649 — Environmental
ParameterValue
Operating ambient temperature68...158 °F (20...70 °C)
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 IEC 60529
37649 — Approvals
ParameterValue
StandardsIEC 60947-2
MPN
37649