Skip to main content
Schneider Electric 60233

Schneider Electric 60233

MPN60233
Obsolete

Multi9 - C60 UL489 - MCB - 1P - 35 A - D Curve - 120 V - 10 kA - ring term

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

60233 key specifications
ParameterValue
Control typeToggle
Network typeDC AC
Product or component typeMiniature circuit-breaker
Voltage500 V AC EN/IEC 60947-2
[Ue] rated operational voltage240 V AC 60 V DC 120 V AC
[Uimp] rated impulse withstand voltage6 kVEN/IEC 60947-2
Breaking capacity5 kA AIR 240 V AC UL 489 10 kA Icu 240 V AC EN/IEC 60947-2 10 kA Icu 240 V AC GB 14048.2 10 kA Icu 60 V DC EN/IEC 60947-2 10 kA Icu 60 V DC GB 14048.2 10 kA AIR 120 V AC UL 489 10 kA AIR 60 V DC UL 489 10 kA AIR 120 V AC CSA C22.2 No 5.2 5 kA AIR 240 V AC CSA C22.2 No 5.2 10 kA AIR 60 V DC CSA C22.2 No 5.2
Line rated current35 A 77 °F (25 °C)
Network frequency50/60 Hz
Poles description1P
Number of protected poles1
IP degree of protectionIP40 (modular enclosure) conforming to IEC 60529 IP10 conforming to IEC 60529

All specifications

60233 additional specifications
ParameterValue
Mounting modeClip-on
Mounting supportDIN rail
Connections - terminalsRing terminal top or bottom)
Pollution degree3 EN/IEC 60947-2
Relative humidity95 % 131 °F (55 °C)
Operating altitude6561.68 ft (2000 m)
ColorGray
Depth2.9 in (73 mm)
Width0.7 in (18 mm)
Height4.8 in (123 mm)
Electrical durability10000 cycles
Mechanical durability20000 cycles
StandardsGB 14048.2 EN/IEC 60947-2 UL 489 CSA C22.2 No 5
RangeMulti9
Category00915-C60N MINIATURE CIRCUIT BREAKER-UL489
Curve codeD
9 mm pitches2
Tropicalisation2 IEC 60068-1
Limitation class3 EN/IEC 60947-2
Local signallingON/OFF indication
Device short nameC60 UL489
Tightening torque17.7 lbf.in (2 N.m) top or bottom
Device applicationDistribution
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Magnetic tripping limit12 x In +/- 20 % AC 17 x In +/- 20 % DC
Provision for padlockingPadlockable
Suitability for isolationYes EN/IEC 60947-2
Contact position indicatorYes
Ambient air temperature for storage-40...176 °F (-40...80 °C)
Ambient air temperature for operation-22...158 °F (-30...70 °C)
MPN