Schneider Electric 65479
MPN65479
Active
protection relay, EasyPact MVS, ET6G
$1,394.12Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
Specifications
| Parameter | Value |
|---|---|
| Network type | AC |
| Protection type | Overload protection (long time) Short time short-circuit protection Earth fault Instantaneous short-circuit protection |
| Range of product | EasyPact MVS |
| Product or component type | Control unit |
| Long time delay adjustment type | Adjustable 9 settings |
| Short-time delay adjustment type | Adjustable 5 settings |
| Ground-fault pick-up adjustment type | Adjustable 9 settings |
| Long time pick-up adjustment type ir | Adjustable 9 settings |
| Short-time pick-up adjustment type isd | Adjustable 9 settings |
| Instantaneous pick-up adjustment type ii | Adjustable 9 settings |
| Ground-fault time delay adjustment type -tg | Adjustable 5 settings |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
All specifications
| Parameter | Value |
|---|---|
| Network frequency | 50/60 Hz |
| Poles description | 4P 3P |
| Protected poles description | 3D + N/2 4D 3D |
| Mounting mode | Fixed Drawout |
| Depth | 75 mm |
| Width | 55 mm |
| Height | 200 mm |
| Thermal memory | 20 minutes before and after tripping |
| Trip unit name | ET6G |
| Fault indication | Short-circuit Overload Earth fault Internal fault |
| Neutral position | Left |
| Trip unit rating | 800...4000 A |
| Trip unit technology | Micro-processor based |
| Neutral protection setting | Without protection (3D) 0.5 x Ir (3D + N/2) 1 x Ir (4D) |
| Circuit breaker application | Industrial Standard |
| Trip unit protection functions | LSIG |
| Zone selective interlocking ZSI | With |
| Long time pick-up adjustment range | 0.4...1 x In |
| Ambient air temperature for storage | -25...85 °C |
| Ambient air temperature for operation | -5...70 °C |
| [Tr] Long-Time delay adjustment range | 0.5...24 s (6 x Ir), accuracy: 0...- 20 % |
| Instantaneous pick-up adjustment range | 2...15 x In, accuracy: +/- 10 % Off |
| [Tsd] Short-Time delay adjustment range | 100...400 ms |
| [Isd] short-time pick-up adjustment range | 1.5...10 x Ir |
| [Ig] ground-fault pick-up adjustment range | 0.2...1 x In (400 A < In =< 1000 A), accuracy: +/- 10 % 500...1200 x In (In >= 1250 A), accuracy: +/- 10 % |
| [Tg] Ground-Fault time delay adjustment range | 100...400 ms |
MPN
65479