Skip to main content
Schneider Electric A9D01610 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9D01610 Acti9 iDPN N Vigi RCBO, 10 A, 30

MPNA9D01610
Active

Schneider Electric Acti9 iDPN N Vigi RCBO, 1P+N, 10 A, 30 mA, C-curve, 6 kA Icn, DIN-rail clip-on, IP20, active production.

$262.10 – $272.59Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9D01610 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Trip unit technologyThermal-magnetic
Local signalling / indicationON, OFF, fault trip
A9D01610 — Electrical Ratings
ParameterValue
Rated current (In)10 A
Rated operational voltage (Ue)110 V AC 50 Hz
Poles description1P + N
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)400 V AC 50 Hz
Rated impulse withstand voltage (Uimp)4 kV
Overvoltage categoryIII conforming to IEC 60364
Device location in systemOutgoer
Electrical durability20000 cycles
Mechanical durability (operating cycles)20000 cycles
A9D01610 — Identification
ParameterValue
Product nameActi9 iDPN Vigi
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiDPN N Vigi
A9D01610 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsSingle terminal top or bottom 1...16 mm² rigid Single terminal top or bottom 1...10 mm² flexible Single terminal top or bottom 1...10 mm² flexible with ferrule
Wire stripping length15 mm for top or bottom connection
Terminal tightening torque2 N.m top or bottom
Width36 mm
Height85 mm
Depth73 mm
A9D01610 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3
Relative humidity95 % at 55 °C
Tropicalisation2 conforming to IEC 60068-1
A9D01610 — Approvals
ParameterValue
StandardsEN/IEC 61009-2-1

Product details

The Schneider Electric A9D01610 is an Acti9 iDPN N Vigi residual-current circuit breaker (RCBO) — a 1P+N device combining overcurrent protection and earth-leakage detection in a single 36 mm wide module. Rated at 10 A with a C-curve (magnetic trip 5–10 × In), it is built for final-subcircuit protection on 50 Hz AC networks. The integrated 30 mA earth-leakage sensitivity covers personnel protection (additional shock-hazard mitigation) per EN/IEC 61009-2-1. Breaking capacity is 6000 A Icn at 110 V AC, which is standard for residential and light-commercial distribution boards — adequate for fault currents typical at the outgoer position. The thermal-magnetic trip unit handles sustained overloads and short-circuits; the residual-current module adds ground-fault detection without needing a separate RCCB upstream.

Clip-on mounting to a DIN rail, 4 modules of 9 mm pitch (36 mm total width). Neutral is on the left; phase and neutral connections are single terminals top and bottom, accepting 1–16 mm² rigid or 1–10 mm² flexible. Tightening torque 2 N·m; strip length 15 mm. The device occupies one standard MCB/RCBO slot in a modular enclosure. IP20 on the terminals (finger-safe), IP40 on the modular enclosure face — suitable for dry indoor distribution boards. Tropicalisation class 2 per IEC 60068-1 means it withstands 95 % RH at 55 °C without condensation damage.

Frequently asked questions

What is the breaking capacity of A9D01610?

The breaking capacity is 6000 A Icn at 110 V AC 50 Hz, conforming to EN/IEC 61009-2-1. This covers typical fault levels in residential and light-commercial distribution boards.

What earth-leakage sensitivity does A9D01610 have?

The integrated earth-leakage protection is set at 30 mA sensitivity, providing personnel shock-hazard mitigation for final subcircuits.

MPN