Schneider Electric A9D02616 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9D02616 Acti9 iDPN Vigi, 16 A, 10 mA, Cu

MPNA9D02616
Active

Schneider Electric Acti9 iDPN Vigi, RCBO, A9D02616, 1P+N, 16 A, 10 mA, Curve C, 6 kA Icn, DIN rail.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9D02616 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)10 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Trip unit technologyThermal-magnetic
Local signalling / indicationON, OFF, fault trip
A9D02616 — Electrical Ratings
ParameterValue
Rated current (In)16 A
Rated operational voltage (Ue)230...240 V AC 50 Hz
Poles description1P + N
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)400 V AC 50 Hz
Rated impulse withstand voltage (Uimp)4 kV
Overvoltage categoryIII conforming to IEC 60364
Device location in systemOutgoer
Electrical durability20000 cycles
Mechanical durability (operating cycles)20000 cycles
A9D02616 — Identification
ParameterValue
Product nameActi9 iDPN Vigi
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiDPN N Vigi
A9D02616 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsSingle terminal top or bottom 1...16 mm² rigid Single terminal top or bottom 1...10 mm² flexible Single terminal top or bottom 1...10 mm² flexible with ferrule
Wire stripping length15 mm for top or bottom connection
Terminal tightening torque2 N.m top or bottom
Width36 mm
Height85 mm
Depth73 mm
A9D02616 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3
Relative humidity95 % at 55 °C
Tropicalisation2 conforming to IEC 60068-1
A9D02616 — Approvals
ParameterValue
StandardsEN/IEC 61009-2-1

Product details

The Schneider Electric A9D02616 is an Acti9 iDPN Vigi residual-current circuit breaker with overcurrent protection (RCBO), combining a 16 A thermal-magnetic trip unit with integrated 10 mA earth-leakage protection in a single 1P+N module. It clips onto a DIN rail, occupies 4 x 9 mm pitches (36 mm wide), and is rated for 6000 A Icn at 230...240 V AC 50 Hz per EN/IEC 61009-2-1.

The 10 mA earth-leakage sensitivity is the standout spec on this part — most RCBOs in this form factor are 30 mA. That 10 mA threshold is typically specified for circuits where a lower fault current must be detected: wet locations, medical equipment in patient areas, or circuits supplying hand-held tools where the body path to ground is low impedance.

Frequently asked questions

What is the A9D02616's earth-leakage sensitivity?

10 mA — that's the trip threshold for the integrated residual-current protection, which is lower than the typical 30 mA found on most RCBOs in this class.

What breaking capacity does the A9D02616 have?

6000 A Icn at 230...240 V AC 50 Hz, conforming to EN/IEC 61009-2-1. That's the standard interrupting rating for final sub-circuits in a domestic or light commercial distribution board.

Where can I buy the A9D02616?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time.

What standards does the A9D02616 comply with?

EN/IEC 61009-2-1 for RCBOs, plus IEC 60068-1 for tropicalisation (class 2) and IEC 60364 for overvoltage category III.

MPN
A9D02616