Schneider Electric A9D01810 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9D01810 Acti9 iC60 RCBO, 10 A, 10 kA, C-

MPNA9D01810
Active

Schneider Electric Acti9 iC60 RCBO, A9D01810, 1P+N, 10 A, 10 kA, C-curve, 10 mA earth leakage, IP20.

$220.94Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9D01810 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)10 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage dependent
Trip unit technologyThermal-magnetic
Local signalling / indicationFault indication ON/OFF indication
A9D01810 — Electrical Ratings
ParameterValue
Rated current (In)10 A at 50 °C
Rated operational voltage (Ue)230/240 V AC 50/60 Hz
Poles description1P + Ns
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)400 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)4 kV
Overvoltage categoryII
Device location in systemOutgoer
Electrical durability5000 cycles
Mechanical durability (operating cycles)20000 cycles
A9D01810 — Identification
ParameterValue
Product nameActi9 iC60 RCBO
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiC60H RCBO PoN
A9D01810 — Mechanical
ParameterValue
Mounting supportIsobar A Isobar B
Mounting modePlug-on
Control typeToggle
Width in 9 mm modules2
Terminal connectionsScrew clamp terminal (top) 1...16 mm² flexible Screw clamp terminal (bottom) 1...10 mm² flexible Screw clamp terminal (top) 1...25 mm² rigid Screw clamp terminal (bottom) 1...16 mm² rigid Plug-on neutral (upstream)
Wire stripping length14 mm for top connection 13 mm for bottom connection
Terminal tightening torque3.5 N.m top 2 N.m bottom
Width18 mm
Height110 mm
Depth72 mm
A9D01810 — Environmental
ParameterValue
Operating ambient temperature-15...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Relative humidity95 % at 55 °C
Tropicalisation2
A9D01810 — Approvals
ParameterValue
StandardsIEC 61009-1 IEC 61009-2-2 BS EN 61009-1

Product details

It combines a C-curve MCB (thermal-magnetic trip, 5–10 x In magnetic threshold) with integrated earth-leakage detection at 10 mA sensitivity, so one device handles both short-circuit and ground-fault protection on a single outgoing circuit. That 10 kA rating is the short-circuit current it can safely interrupt under IEC 61009-2-2 — enough for most final subcircuits in a TN earthing system. The 10 mA leakage sensitivity makes it suitable for circuits where a 30 mA device would be too coarse, such as lighting or small loads in wet or high-integrity areas.

IP20 rated for the terminals; IP40 inside a modular enclosure.

Frequently asked questions

What are the key ratings of A9D01810?

10 A rated current, 10 kA breaking capacity at 240 V AC, C-curve, 10 mA earth-leakage sensitivity, 1P+N poles, thermal-magnetic trip.

Where can I buy A9D01810 and get a price?

This part is sourced and quoted to order against an RFQ through our independent distribution channel. Submit a request for current pricing and availability.

What compliance standards does A9D01810 meet?

It conforms to IEC 61009-1, IEC 61009-2-2, and BS EN 61009-1. The IP rating is IP20 per IEC 60529.

MPN