Schneider Electric A9D02816 — Residual Current Breakers (RCCB/RCBO)

A9D02816 Acti9 iC60 RCBO, 16 A C-curve 30 mA, 10 kA

MPNA9D02816
Active

Schneider Electric Acti9 iC60H RCBO, A9D02816, 1P + Ns, 16 A rated at 50 °C, C-curve, 30 mA earth-leakage sensitivity, 10 kA Icn breaking capacity at 240 V AC, clip-on DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9D02816 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage dependent
Trip unit technologyThermal-magnetic
Local signalling / indicationON/OFF indication
A9D02816 — Electrical Ratings
ParameterValue
Rated current (In)16 A at 50 °C
Rated operational voltage (Ue)230/240 V AC 50/60 Hz
Poles description1P + Ns
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)400 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)4 kV
Device location in systemOutgoer
Electrical durability5000 cycles
Mechanical durability (operating cycles)20000 cycles
A9D02816 — Identification
ParameterValue
Product nameActi9 iC60 RCBO
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiC60H RCBO
A9D02816 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules2
Terminal connectionsScrew clamp terminal (top) 1...25 mm² rigid Screw clamp terminal (top) 1...16 mm² flexible Screw clamp terminal (bottom) 1...16 mm² rigid without cable end Screw clamp terminal (bottom) 1...10 mm² flexible
Wire stripping lengthPower circuit: 13 mm for bottom connection Power circuit: 14 mm for top connection
Terminal tightening torquePower circuit: 3.5 N.m top Power circuit: 2 N.m bottom
Width18 mm
Height110 mm
Depth77.5 mm
A9D02816 — Environmental
ParameterValue
Operating ambient temperature-15...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 IP40 (modular enclosure)
Relative humidity95 % at 55 °C
Tropicalisation2
A9D02816 — Approvals
ParameterValue
StandardsIEC 61009-1 IEC 61009-2-2

Product details

It protects a single-phase outgoing circuit against both overload/short-circuit (thermal-magnetic trip, C-curve) and earth leakage (30 mA sensitivity, integrated). Rated 16 A at 50 °C with a breaking capacity of 10 kA Icn at 240 V AC, it is sized for residential and light commercial distribution boards where the prospective fault current stays under 10 kA. The C-curve characteristic (trips at 5–10× In) suits inductive loads like small motors, fluorescent lighting banks, and pump circuits — the standard choice for general-purpose socket outlets and fixed equipment in IEC markets.

Clip-on mounting to a 45 mm grid DIN rail. Occupies 2 × 9 mm pitches (18 mm total width). Neutral is on the left (1P + Ns configuration). Screw-clamp terminals: top accepts 1–25 mm² rigid (1–16 mm² flexible), bottom accepts 1–16 mm² rigid (1–10 mm² flexible). Tightening torque 3.5 N.m top, 2 N.m bottom. Wire stripping length 14 mm top, 13 mm bottom. IP20 rated; IP40 in a modular enclosure.

Certified to IEC 61009-1 and IEC 61009-2-2 (the RCBO product standard). Rated for TN earthing systems, AC network, 50 Hz. Limitation class 3 (energy-limiting performance).

Frequently asked questions

What is the breaking capacity of A9D02816?

The A9D02816 has a breaking capacity of 10,000 A Icn at 240 V AC, 50/60 Hz, which means it can safely interrupt fault currents up to that level without damage.

What earth-leakage sensitivity does A9D02816 have?

The integrated earth-leakage protection is set at 30 mA sensitivity, providing personal protection against indirect contact and fire risk from leakage currents.