It protects a single-phase outgoing circuit against both overload/short-circuit (thermal-magnetic trip, C-curve) and earth leakage (30 mA sensitivity, integrated). Rated 16 A at 50 °C with a breaking capacity of 10 kA Icn at 240 V AC, it is sized for residential and light commercial distribution boards where the prospective fault current stays under 10 kA. The C-curve characteristic (trips at 5–10× In) suits inductive loads like small motors, fluorescent lighting banks, and pump circuits — the standard choice for general-purpose socket outlets and fixed equipment in IEC markets.
Clip-on mounting to a 45 mm grid DIN rail. Occupies 2 × 9 mm pitches (18 mm total width). Neutral is on the left (1P + Ns configuration). Screw-clamp terminals: top accepts 1–25 mm² rigid (1–16 mm² flexible), bottom accepts 1–16 mm² rigid (1–10 mm² flexible). Tightening torque 3.5 N.m top, 2 N.m bottom. Wire stripping length 14 mm top, 13 mm bottom. IP20 rated; IP40 in a modular enclosure.
Certified to IEC 61009-1 and IEC 61009-2-2 (the RCBO product standard). Rated for TN earthing systems, AC network, 50 Hz. Limitation class 3 (energy-limiting performance).