It protects a single-phase outgoing circuit against overload, short-circuit, and earth leakage, all in one DIN-rail footprint. The integrated earth-leakage protection trips at 30 mA sensitivity, covering personnel protection for TN earthing systems. Clip it onto a DIN rail, land the line and load on the screw-clamp terminals (top accepts up to 25 mm² rigid), and it's ready for a panel. The toggle gives local ON/OFF indication and accepts a 4 mm padlock for lockout.
The 6 A rating with B-curve means this RCBO is sized for lighting or small resistive loads — not motor circuits. If your panel's fault level is higher, step up to the iC60N or iC60L variants. IP20 on the front, IP40 inside the modular enclosure.