Schneider Electric A9D04832 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9D04832 Acti9 iC60 RCBO, 32A B-Curve, 30

MPNA9D04832
Active

Schneider Electric Acti9 iC60H RCBO, 1P + N, 32 A, B-curve, 30 mA earth leakage, 10 kA breaking capacity, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9D04832 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage dependent
Trip unit technologyThermal-magnetic
Local signalling / indicationON/OFF indication
A9D04832 — Electrical Ratings
ParameterValue
Rated current (In)32 A at 50 °C
Rated operational voltage (Ue)230/240 V AC 50/60 Hz
Poles description1P + Ns
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)400 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)4 kV
Device location in systemOutgoer
Electrical durability5000 cycles
Mechanical durability (operating cycles)20000 cycles
A9D04832 — Identification
ParameterValue
Product nameActi9 iC60 RCBO
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiC60H RCBO
A9D04832 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules2
Terminal connectionsScrew clamp terminal (top) 1...25 mm² rigid without cable end Screw clamp terminal (top) 1...16 mm² flexible Screw clamp terminal (bottom) 1...16 mm² rigid Screw clamp terminal (bottom) 1...10 mm² flexible
Wire stripping lengthPower circuit: 13 mm for bottom connection Power circuit: 14 mm for top connection
Terminal tightening torquePower circuit: 3.5 N.m top Power circuit: 2 N.m bottom
Width18 mm
Height110 mm
Depth77.5 mm
A9D04832 — Environmental
ParameterValue
Operating ambient temperature-15...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 IP40 (modular enclosure)
Relative humidity95 % at 55 °C
Tropicalisation2
A9D04832 — Approvals
ParameterValue
StandardsIEC 61009-1 IEC 61009-2-2

Product details

It protects a single-phase outgoing circuit against overloads, short-circuits, and earth leakage, all in one DIN-rail unit that clips onto the standard 45 mm grid. The integrated earth-leakage protection is set at 30 mA sensitivity, which is the standard threshold for personal protection against indirect contact.

Height is 110 mm, depth 77.5 mm — verify the gland plate clearance in shallow enclosures, as the 77.5 mm depth plus wiring space can be tight in a 100 mm deep box. IP20 rated for the body, IP40 for the modular enclosure; fine for dry indoor panels, not for washdown zones.

Standards compliance and documentation

Designed and tested to IEC 61009-1 and IEC 61009-2-2, which cover RCBOs for household and similar installations. The TN earthing system compatibility is stated, meaning it works with solidly-grounded neutral systems common in commercial buildings. The thermal-magnetic trip unit gives a standard dual-response curve: thermal for overloads, magnetic for short-circuits. No separate UL or CSA listing is stated in the evidence; if you need a UL 489 or CSA C22.2 listed device, verify the specific approval mark on the nameplate before specifying.

Frequently asked questions

What is A9D04832's listed depth?

The depth is 77.5 mm, measured from the DIN-rail mounting surface to the front face of the toggle.

What compliance standards does A9D04832 meet?

It is designed and tested to IEC 61009-1 and IEC 61009-2-2, the international standards for RCBOs. The evidence does not list separate RoHS, REACH, UL, or CSA declarations — verify the specific markings on the unit or request compliance documentation at quote time.

MPN