Skip to main content
Schneider Electric A9D05616 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9D05616 Acti9 iDPN Vigi, 16A C-curve 10m

MPNA9D05616
Obsolete

Schneider Electric Acti9 iDPN Vigi RCBO, 1P+N, 16 A, C-curve, 10 mA earth-leakage sensitivity, 4.5 kA breaking capacity, clip-on DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9D05616 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)10 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Trip unit technologyThermal-magnetic
Local signalling / indicationON, OFF, fault trip
A9D05616 — Electrical Ratings
ParameterValue
Rated current (In)16 A
Rated operational voltage (Ue)230...240 V AC 50 Hz
Poles description1P + N
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)400 V AC 50 Hz
Rated impulse withstand voltage (Uimp)4 kV
Overvoltage categoryIII conforming to IEC 60364
Device location in systemOutgoer
Electrical durability20000 cycles
Mechanical durability (operating cycles)20000 cycles
A9D05616 — Identification
ParameterValue
Product nameActi9 iDPN Vigi
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiDPNa Vigi
A9D05616 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsSingle terminal top or bottom 1...16 mm² rigid Single terminal top or bottom 1...10 mm² flexible Single terminal top or bottom 1...10 mm² flexible with ferrule
Wire stripping length15 mm for top or bottom connection
Terminal tightening torque2 N.m top or bottom
Width36 mm
Height85 mm
Depth73 mm
A9D05616 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3
Relative humidity95 % at 55 °C
Tropicalisation2 conforming to IEC 60068-1
A9D05616 — Approvals
ParameterValue
StandardsEN/IEC 61009-2-1

Product details

It protects a single outgoing circuit (distribution application, outgoer position per) against overload, short-circuit, and earth leakage, all in one clip-on DIN-rail unit. The thermal-magnetic trip unit gives the C-curve response (magnetic tripping at 5...10 x In,), and the integrated earth-leakage protection is fixed at 10 mA sensitivity.

Rated 16 A with a 4500 A Icn breaking capacity at 230...240 V AC, 50 Hz per EN/IEC 61009-2-1. The 10 mA sensitivity suits circuits requiring a low leakage threshold.

Clip-on mounting onto standard DIN rail. The module occupies 4 x 9 mm pitches — 36 mm wide, 85 mm tall, 73 mm deep. Single terminal top or bottom accepts 1...16 mm² rigid or 1...10 mm² flexible cable; wire strip length is 15 mm, tightening torque 2 N.m. Neutral is on the left. IP20 on the device body, IP40 inside a modular enclosure — so it's a panel-mount part, not for wet locations without an outer enclosure.

Designed to EN/IEC 61009-2-1. Relative humidity 95% at 55 °C. Local signalling shows ON, OFF, and fault trip. Electrical and mechanical durability both rated at 20,000 cycles.

Frequently asked questions

What is the breaking capacity of A9D05616?

The breaking capacity is 4500 A Icn at 230...240 V AC, 50 Hz, conforming to EN/IEC 61009-2-1.

What earth-leakage sensitivity does A9D05616 have?

The integrated earth-leakage protection is fixed at 10 mA sensitivity.

MPN
A9D05616