Schneider Electric A9D06810 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9D06810 Acti9 iC60 RCBO, 10 A C-Curve, 1

MPNA9D06810
Active

Schneider Electric Acti9 iC60H RCBO, 1P+N, 10 A, C-curve, 100 mA earth leakage, 10 kA breaking capacity.

$209.26Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9D06810 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)100 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage dependent
Trip unit technologyThermal-magnetic
Local signalling / indicationON/OFF indication Fault indication
A9D06810 — Electrical Ratings
ParameterValue
Rated current (In)10 A at 50 °C
Rated operational voltage (Ue)230/240 V AC 50/60 Hz
Poles description1P + Ns
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)400 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)4 kV
Overvoltage categoryII
Device location in systemOutgoer
Electrical durability5000 cycles
Mechanical durability (operating cycles)20000 cycles
A9D06810 — Identification
ParameterValue
Product nameActi9 iC60 RCBO
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiC60H RCBO PoN
A9D06810 — Mechanical
ParameterValue
Mounting supportIsobar B Isobar A
Mounting modePlug-on
Control typeToggle
Width in 9 mm modules2
Terminal connectionsScrew clamp terminal (top) 1...16 mm² flexible Screw clamp terminal (bottom) 1...10 mm² flexible Screw clamp terminal (top) 1...25 mm² rigid Screw clamp terminal (bottom) 1...16 mm² rigid Plug-on neutral (upstream)
Wire stripping length14 mm for top connection 13 mm for bottom connection
Terminal tightening torque3.5 N.m top 2 N.m bottom
Width18 mm
Height110 mm
Depth72 mm
A9D06810 — Environmental
ParameterValue
Operating ambient temperature-15...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Relative humidity95 % at 55 °C
Tropicalisation2
A9D06810 — Approvals
ParameterValue
StandardsIEC 61009-2-2 BS EN 61009-1 IEC 61009-1

Product details

It combines a 10 A thermal-magnetic MCB (C-curve, magnetic trip 5–10 x In) with integrated 100 mA earth-leakage protection, all in a 1P+N form factor with the neutral on the left.

Where it lives in the panel

It fits into an Isobar A or Isobar B distribution board as an outgoer device. The screw-clamp torque spec is 3.5 N·m top, 2 N·m bottom. Strip length is 14 mm for the top connection, 13 mm for the bottom. IP20 finger-safe with the modular enclosure in place; IP40 inside the enclosure.

That means it's still a standard BOM line, not a last-time-buy scavenger hunt. If you're freezing a panel design or topping up spares, this one isn't going anywhere soon.

Built and certified to IEC 61009-1, IEC 61009-2-2, and BS EN 61009-1 — the harmonized standards for RCBOs. Rated for TN earthing systems. Overvoltage category II, so it's intended for final circuits fed from a distribution board, not the service entrance.

Rated for 5,000 electrical cycles and 20,000 mechanical cycles. That's enough for a typical commercial lighting or small-power circuit where it sees a few operations a week — not a daily-switched load like a motor starter.

Frequently asked questions

What is the breaking capacity of A9D06810?

10,000 A Icn at 240 V AC, 50/60 Hz, conforming to IEC 61009-2-2. That's the standard fault-interruption rating for a final-circuit RCBO in a domestic or commercial distribution board.

What earth-leakage sensitivity does this RCBO have?

100 mA sensitivity, integrated into the same 18 mm-wide unit. That's a common choice for general-purpose socket-outlet circuits or lighting where you want ground-fault protection but need to avoid nuisance tripping from normal leakage.

Where can I buy A9D06810 and what is the lead time?

Sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm lead-time and price.

What compliance documentation does Schneider provide for A9D06810?

The RCBO is certified to IEC 61009-1, IEC 61009-2-2, and BS EN 61009-1. Standard documentation includes the declaration of conformity and the product datasheet. RoHS and REACH compliance are standard for the Acti9 range.

MPN