Skip to main content
Schneider Electric A9D06816 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9D06816 Acti9 iC60 RCBO, 16 A, 10 kA, 10

MPNA9D06816
Active

Schneider Electric Acti9 iC60H RCBO PoN, 1P + Ns, 16 A, C-curve, 10 kA Icn at 240 V AC, 100 mA earth-leakage sensitivity, thermal-magnetic trip, plug-on mounting.

$209.26Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9D06816 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)100 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage dependent
Trip unit technologyThermal-magnetic
Local signalling / indicationFault indication ON/OFF indication
A9D06816 — Electrical Ratings
ParameterValue
Rated current (In)16 A at 50 °C
Rated operational voltage (Ue)230/240 V AC 50/60 Hz
Poles description1P + Ns
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)400 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)4 kV
Overvoltage categoryII
Device location in systemOutgoer
Electrical durability5000 cycles
Mechanical durability (operating cycles)20000 cycles
A9D06816 — Identification
ParameterValue
Product nameActi9 iC60 RCBO
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiC60H RCBO PoN
A9D06816 — Mechanical
ParameterValue
Mounting supportIsobar A Isobar B
Mounting modePlug-on
Control typeToggle
Width in 9 mm modules2
Terminal connectionsScrew clamp terminal (top) 1...16 mm² flexible Screw clamp terminal (bottom) 1...10 mm² flexible Screw clamp terminal (top) 1...25 mm² rigid Screw clamp terminal (bottom) 1...16 mm² rigid Plug-on neutral (upstream)
Wire stripping length14 mm for top connection 13 mm for bottom connection
Terminal tightening torque3.5 N.m top 2 N.m bottom
Width18 mm
Height110 mm
Depth72 mm
A9D06816 — Environmental
ParameterValue
Operating ambient temperature-15...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Relative humidity95 % at 55 °C
Tropicalisation2
A9D06816 — Approvals
ParameterValue
StandardsBS EN 61009-1 IEC 61009-1 IEC 61009-2-2

Product details

It protects a single pole (1P + Ns) outgoing circuit against overload, short-circuit, and earth leakage, all in one DIN-rail footprint. Earth-leakage protection is integrated at 100 mA sensitivity — a common specification for circuits feeding socket outlets or general-purpose equipment where 30 mA personal protection isn't mandated, but some ground-fault coverage is still wanted.

Plug-on mounting onto Isobar A or Isobar B distribution boards. The 18 mm width (2 × 9 mm pitches) matches the standard modular grid — one RCBO per outgoing way. Neutral is on the left, and the upstream connection uses a plug-on neutral tail, so no separate neutral bar link is needed on compatible boards. Torque to 3.5 N·m top, 2 N·m bottom. Strip length 14 mm top, 13 mm bottom. IP20 finger-safe, IP40 inside the modular enclosure.

Designed and certified to BS EN 61009-1, IEC 61009-1, and IEC 61009-2-2 — the harmonised standards for RCBOs. Tropicalisation class 2, overvoltage category II, rated for TN earthing systems.

Frequently asked questions

How do I get pricing and availability for A9D06816?

Submit an RFQ against this order code. The part is sourced through independent distribution channels; current pricing and stock position are confirmed at quote time.

What is the breaking capacity of the A9D06816?

10,000 A Icn at 240 V AC, 50/60 Hz, conforming to IEC 61009-2-2. That is the rated short-circuit capacity — it can safely interrupt a fault up to 10 kA without upstream devices needing to clear it.

What does the C-curve mean on this RCBO?

The C-curve magnetic trip operates between 5 and 10 times the rated current (In). For a 16 A unit, that means the instantaneous magnetic release picks up between 80 A and 160 A — a good match for circuits with moderate inrush like small motors, contactors, or lighting banks.

What earth-leakage sensitivity does the A9D06816 provide?

100 mA residual current sensitivity. This is typically used for general-purpose sub-circuits where 30 mA personal protection is not required by local code, but some ground-fault detection is still wanted to prevent equipment damage or fire risk.

MPN