Skip to main content
Schneider Electric A9D73625T — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9D73625T Acti9 ISPN Vigi RCBO, 25A C-Cur

MPNA9D73625T
Active

Schneider Electric Acti9 ISPN Vigi, RCBO, 25A, C-curve, 30mA earth leakage, 1P+N, 6kA Icn at 230/240V AC, clip-on DIN rail.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9D73625T — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage dependent
Trip unit technologyThermal-magnetic
Local signalling / indicationON/OFF indication
A9D73625T — Electrical Ratings
ParameterValue
Rated current (In)25 A
Rated operational voltage (Ue)230/240 V AC 50 Hz
Poles description1P + N
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)500 V AC 50 Hz
Rated impulse withstand voltage (Uimp)4 kV
Device location in systemOutgoer
Electrical durability6000 cycles
Mechanical durability (operating cycles)10000 cycles
A9D73625T — Identification
ParameterValue
Product nameISPN Vigi
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
A9D73625T — Mechanical
ParameterValue
Mounting supportDIN rail Chassis
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules2
Terminal connectionsTunnel type terminal (upstream) 1...25 mm² rigid Tunnel type terminal (downstream) 1...16 mm² rigid Tunnel type terminal (upstream) 1...16 mm² flexible Tunnel type terminal (downstream) 1...10 mm² flexible
Wire stripping length13 mm for downstream connection 14 mm for upstream connection
Terminal tightening torque3.5 N.m upstream 2 N.m downstream
Width18 mm
A9D73625T — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20
Pollution degree2
Relative humidity95 % at 55 °C
Tropicalisation2
A9D73625T — Approvals
ParameterValue
StandardsAS/NZS 61009.1

Product details

The Schneider Electric A9D73625T is a 1P+N residual current breaker with overcurrent protection (RCBO) from the Acti9 ISPN Vigi range, combining a 25 A thermal-magnetic MCB (C-curve, 5–10× In magnetic trip) with integrated 30 mA earth-leakage protection in a single 18 mm wide module. The C-curve characteristic (5–10× In magnetic trip) suits inductive loads like small motors, fluorescent lighting banks, and transformer-fed circuits where inrush current exceeds the B-curve threshold.

Clip-on mounting to DIN rail or chassis, 18 mm width (2× 9 mm pitches), occupies a single modular slot in the distribution board. Neutral on the left, tunnel-type terminals accept 1–25 mm² rigid upstream and 1–16 mm² rigid downstream; flexible cable capacity is 1–16 mm² upstream and 1–10 mm² downstream. Wire stripping length is 14 mm upstream, 13 mm downstream. Tightening torque: 3.5 N·m upstream, 2 N·m downstream. Padlockable with Ø 4 mm padlock for lockout/tagout.

Compliant with AS/NZS 61009.1, the Australian/New Zealand standard for RCBOs. Electrical durability 6000 cycles, mechanical durability 10000 cycles — typical for a 25 A residential-grade RCBO. Limitation class 3 (energy limiting) for downstream cable protection.

Frequently asked questions

What is the A9D73625T used for?

It is a combined overcurrent and earth-leakage protection device (RCBO) for 230/240 V AC final circuits in TN earthing systems, protecting against both overload/short-circuit and 30 mA earth faults in a single 18 mm module.

What is the breaking capacity of the A9D73625T?

6000 A Icn at 230/240 V AC 50 Hz — sufficient for most residential and light commercial sub-distribution boards in Australia and New Zealand.