Skip to main content
Schneider Electric A9F03110

Schneider A9F03110 Acti9 iC60N MCB, 1-pole B-curve 10 A, 36 kA

MPNA9F03110
Obsolete

Schneider Electric Acti9 iC60N A9F03110 miniature circuit breaker, 1-pole, B-curve, 10 A rated current, 36 kA Icu breaking capacity, screw terminals, DIN-rail mount, IP20.

$14.97 – $16.27Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

A9F03110 key specifications
ParameterValue
Control typeToggle
Network typeAC DC
Product or component typeMiniature circuit-breaker
Voltage500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2
Breaking capacity36 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2 10 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
Current10 A
[Ics] rated service breaking capacity27 kA 75 % conforming to EN/IEC 60947-2 - 12...60 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 100...133 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - 12...60 V DC 10 kA 100 % conforming to EN/IEC 60947-2 - 60...72 V DC
Network frequency50/60 Hz
Poles description1P
Number of protected poles1
Utilisation categoryCategory A conforming to EN/IEC 60947-2

All specifications

A9F03110 additional specifications
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
Mounting supportDIN rail
Wire stripping length14 mm for top or bottom connection
Connections - terminalsDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
Depth78.5 mm
Width18 mm
ColorWhite
Height91 mm
Electrical durability10000 cycles
Mechanical durability20000 cycles
StandardsEN/IEC 60947-2 EN/IEC 60898-1
RangeActi9
Curve codeB
9 mm pitches2
Tropicalisation2 conforming to IEC 60068-1
Limitation class3 conforming to EN/IEC 60898-1
Local signallingTrip indicator
Device short nameIC60N
Tightening torque2 N.m top or bottom
Device applicationDistribution
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Magnetic tripping limit4 x In +/- 20 %
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Contact position indicatorYes
Ambient air temperature for storage-40...85 °C
Ambient air temperature for operation-35...70 °C

Product details

Overview

The A9F03110 is a 1-pole B-curve miniature circuit breaker from the Schneider Acti9 iC60N range, rated 10 A with a 36 kA breaking capacity (Icu) under IEC 60947-2. It carries dual certification to both IEC 60947-2 and IEC 60898-1, covering distribution and industrial motor-starting duty.

MPN
A9F03110