Skip to main content
Schneider Electric A9F03120

Schneider Electric A9F03120

MPNA9F03120
Obsolete

Circuit Breaker iC60N, 20A, B, IP20

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

A9F03120 key specifications
ParameterValue
Control typeToggle
Network typeDC AC
Product or component typeMiniature circuit-breaker
Voltage500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2
Breaking capacity36 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2 10 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
Current20 A
[Ics] rated service breaking capacity27 kA 75 % conforming to EN/IEC 60947-2 - 12...60 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 100...133 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - 12...60 V DC 10 kA 100 % conforming to EN/IEC 60947-2 - 60...72 V DC
Network frequency50/60 Hz
Poles description1P
Number of protected poles1
Utilisation categoryCategory A conforming to EN/IEC 60947-2

All specifications

A9F03120 additional specifications
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
Mounting supportDIN rail
Wire stripping length14 mm for top or bottom connection
Connections - terminalsDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
Depth78.5 mm
Width18 mm
ColorWhite
Height91 mm
Electrical durability10000 cycles
Mechanical durability20000 cycles
StandardsEN/IEC 60947-2 EN/IEC 60898-1
RangeActi9
Curve codeB
9 mm pitches2
Tropicalisation2 conforming to IEC 60068-1
Limitation class3 conforming to EN/IEC 60898-1
Local signallingTrip indicator
Device short nameIC60N
Tightening torque2 N.m top or bottom
Device applicationDistribution
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Magnetic tripping limit4 x In +/- 20 %
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Contact position indicatorYes
Ambient air temperature for storage-40...85 °C
Ambient air temperature for operation-35...70 °C
MPN
A9F03120