Specifications

A9KR13440S — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType AC
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
A9KR13440S — Electrical Ratings
ParameterValue
Rated current (In)40 A
Rated operational voltage (Ue)380...415 V AC 50 Hz
Poles description4P
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)440 V AC 50 Hz
Rated impulse withstand voltage (Uimp)4 kV
Device location in systemGroup incomer
Electrical durabilityAC-1: 4000 cycles
Mechanical durability (operating cycles)5000 cycles
A9KR13440S — Identification
ParameterValue
Product nameActi9 ID K
Product / component typeResidual current circuit breaker (RCCB)
Product range / familyActi9
Device short nameID K
A9KR13440S — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules8
Terminal connectionsBiconnect top or bottom 1...35 mm² rigid Biconnect top or bottom 1...25 mm² flexible
Wire stripping length14 mm for top or bottom connection
Terminal tightening torque3.5 N.m top or bottom
Width72 mm
Height81 mm
Depth68 mm
A9KR13440S — Environmental
ParameterValue
Operating ambient temperature-5...55 °C
Storage ambient temperature-25...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree2
Relative humidity95 % at 55 °C
Tropicalisation2 conforming to IEC 60068-1
A9KR13440S — Approvals
ParameterValue
StandardsEN/IEC 61008-1 SS 97:part 1

Product details

RCCB for group incomer duty

The Schneider Electric A9KR13440S is a 4-pole residual current circuit breaker (RCCB) from the Acti9 ID K range, rated 40 A with 30 mA earth-leakage sensitivity. The unit is voltage-independent, so the trip mechanism operates regardless of the supply voltage, which is a reliability advantage on circuits where voltage may sag during a fault. The breaking and making capacity is rated at Idm 500 A / Im 500 A. This positions it as a group incomer or sub-distribution RCCB for three-phase, 4-wire systems in residential, commercial, or light industrial panels.

Neutral is on the left. The IP20 rating suits enclosed panel installation; the modular enclosure achieves IP40 within the panel.

Frequently asked questions

What are the key ratings of A9KR13440S?

Rated current 40 A, earth-leakage sensitivity 30 mA, Type AC, operational voltage 380-415 V AC, breaking capacity Idm 500 A / Im 500 A.

MPN