Specifications

A9KR13225 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType AC
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
A9KR13225 — Electrical Ratings
ParameterValue
Rated current (In)25 A
Rated operational voltage (Ue)220...240 V AC 50 Hz
Poles description2P
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)440 V AC 50 Hz
Rated impulse withstand voltage (Uimp)4 kV
Device location in systemGroup incomer
Electrical durabilityAC-1: 4000 cycles
Mechanical durability (operating cycles)5000 cycles
A9KR13225 — Identification
ParameterValue
Product nameActi9 ID K
Product / component typeResidual current circuit breaker (RCCB)
Product range / familyActi9
Device short nameID K
A9KR13225 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsBiconnect top or bottom 1...35 mm² rigid Biconnect top or bottom 1...25 mm² flexible
Wire stripping length14 mm for top or bottom connection
Terminal tightening torque3.5 N.m top or bottom
Width36 mm
Height81 mm
Depth68 mm
A9KR13225 — Environmental
ParameterValue
Operating ambient temperature-5...55 °C
Storage ambient temperature-25...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree2
Relative humidity95 % at 55 °C
Tropicalisation2 conforming to IEC 60068-1
A9KR13225 — Approvals
ParameterValue
StandardsEN/IEC 61008-1 SS 97:part 1

Product details

The Schneider Electric A9KR13225 is a 2-pole residual current circuit breaker (RCCB) from the Acti9 ID K series, rated 25 A with 30 mA earth-leakage sensitivity. Its IP20 body is rated for indoor panel use; with an optional modular enclosure it reaches IP40. Rated breaking and making capacity is Idm 500 A / Im 500 A, and the device withstands an 8/20 µs impulse current of 200 A per EN/IEC 61008-1. Pollution degree 2 suits it for normal industrial or commercial environments where only non-conductive pollution occurs.

This RCCB is designated as a group incomer — it sits at the head of a sub-distribution board or as the main residual-current protection for a group of final circuits. The clip-on DIN-rail mount and 36 mm width (4 x 9 mm pitches) make it a direct swap into standard Acti9 distribution boards or any 35 mm DIN-rail enclosure. Terminals accept 1–35 mm² rigid or 1–25 mm² flexible conductors, with a stripping length of 14 mm and tightening torque of 3.5 N·m. The biconnect design allows looping through top or bottom without additional terminal blocks — useful for daisy-chaining downstream MCBs or RCBOs.

Frequently asked questions

What is A9KR13225's listed depth (68 mm) on this component line?

The depth is 68 mm, with a height of 81 mm and width of 36 mm (4 module pitches).

What is A9KR13225's listed range (Acti9) on this component line?

It belongs to the Acti9 range, specifically the Acti9 ID K series of residual current circuit breakers.

What compliance documentation does this brand provide for A9KR13225 (RoHS, REACH, UL, IEC)?

The RCCB is certified to EN/IEC 61008-1 and SS 97:part 1, carries a SAFETY Mark, and is tropicalised per IEC 60068-1 class 2. RoHS and REACH declarations are typically available from the manufacturer upon request.

MPN
A9KR13225