Skip to main content
Schneider Electric A9N18457

Schneider A9N18457 Acti9 C120 MCB, 80 A 2P C-curve

MPNA9N18457
Active

Schneider Electric Acti9 C120 miniature circuit-breaker, A9N18457, 80 A, 2P, C-curve, thermal-magnetic, 15 kA Icn.

$152.40 – $274.00Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

A9N18457 key specifications
ParameterValue
Control typeToggle
Network typeAC
Product or component typeMiniature circuit-breaker
Voltage500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Ue] rated operational voltage380...415 V AC 50/60 Hz 220...240 V AC 50/60 Hz 440 V AC 50/60 Hz 230...400 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2
Breaking capacity15000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2
Current80 A at 30 °C
[Ics] rated service breaking capacity7500 A 50 % conforming to EN/IEC 60898-1 - 400 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 15 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC
Network frequency50/60 Hz
Poles description2P
Number of protected poles2

All specifications

A9N18457 additional specifications
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
Mounting modeClip-on
Mounting support35 mm symmetrical DIN rail
Wire stripping length15 mm
Connections - terminalsTunnel type terminals1...50 mm² rigid Tunnel type terminals1.5...35 mm² flexible
Pollution degree3 conforming to IEC 60947-2
Relative humidity95 % at 55 °C
Operating altitude2000 m
Depth73 mm
Width54 mm
ColorWhite
Height81 mm
Electrical durability5000 cycles conforming to IEC 60947-2
Mechanical durability20000 cycles
StandardsEN/IEC 60898-1 EN/IEC 60947-2
RangeActi9
Curve codeC
9 mm pitches6
Tropicalisation2 conforming to IEC 60068-1
Limitation class3 conforming to EN/IEC 60947-2
Local signallingON/OFF indication
Neutral positionLeft
Device short nameC120H
Tightening torque3.5 N.m
Device applicationDistribution
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Magnetic tripping limit5...10 x In
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to IEC 60947-2
Contact position indicatorYes
Locking options descriptionHandle sealable with cable diameter 0.7mm in OFF or ON position
Ambient air temperature for storage-40...70 °C
Ambient air temperature for operation-30...60 °C
Comb busbar and distribution block compatibilityYES

Product details

The Schneider Electric A9N18457 is a miniature circuit-breaker from the Acti9 C120 range, rated 80 A at 30 °C with a C-curve trip characteristic (5–10 × In) and two protected poles, neutral on the left. Out here in the panel, it handles motor and distribution loads without the nuisance trips a B-curve would throw on a compressor start. Breaking capacity hits 15 kA Icn under EN/IEC 60898-1 at 400 V, and up to 30 kA Icu under EN/IEC 60947-2 at 240 V — enough for most light commercial panels. It's class 3 limitation, so let-through energy stays low during a short-circuit event.

Mounting and wiring realities

Clips onto 35 mm symmetrical DIN rail, occupies 6 module pitches (54 mm wide). Terminals accept up to 50 mm² rigid or 35 mm² flexible, tunnel type. IP20 finger-safe for the panel face, but don't spray it with washdown — that's not its job.

Frequently asked questions

What is the breaking capacity of the A9N18457?

It has a rated short-circuit capacity (Icn) of 15 kA at 400 V AC per EN/IEC 60898-1, and an ultimate breaking capacity (Icu) of 30 kA at 240 V AC per EN/IEC 60947-2.

What standards does the A9N18457 comply with?

It complies with EN/IEC 60898-1 and EN/IEC 60947-2 for overcurrent protection and performance, plus pollution degree 3 and tropicalisation class 2 per IEC 60068-1.

What arc fault/earth leakage protection does it offer?

This is a thermal-magnetic MCB only. Earth-leakage protection requires a separate Vigi block. No internal arc fault detection.

MPN
A9N18457