Schneider Electric A9N18572
MPNA9N18572
Active
Add-on residual current device, Acti9 Vigi C120, 2P, 125A, A type, instantaneous, 30mA, 230...240VAC
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026
Specifications
| Parameter | Value |
|---|---|
| Network type | AC |
| Product or component type | Add-on residual current device |
| Voltage | 500 V AC 50/60 Hz conforming to IEC 60947-1 |
| [Ue] rated operational voltage | 230...240 V AC 50/60 Hz |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
| Current | 125 A |
| Residual current tripping technology | Voltage independent |
| Network frequency | 50/60 Hz |
| Poles description | 2P |
| IP degree of protection | IP20 |
| Mounting mode | Clip-on |
| Mounting support | 35 mm symmetrical DIN rail |
All specifications
| Parameter | Value |
|---|---|
| Wire stripping length | 15 mm |
| Connections - terminals | Tunnel type terminals 1...35 mm² flexible Tunnel type terminals 1...50 mm² rigid |
| Electrical connection to MCB | By screws |
| Pollution degree | 3 conforming to IEC 60947-2 |
| Depth | 73 mm |
| Width | 117 mm |
| Color | White |
| Height | 95 mm |
| Product weight | 0.325 kg |
| Mechanical durability | 20000 cycles |
| Standards | EN 61009 IEC/EN 61009-2-1 |
| Range | Acti9 |
| 9 mm pitches | 7 |
| Device short name | Vigi C120 |
| Tightening torque | 3.5 N.m |
| Device location in system | Outgoer Group incomer |
| Earth-leakage sensitivity | 30 mA |
| Earth-leakage protection class | Type A |
| Ambient air temperature for storage | -40...60 °C |
| Earth-leakage protection time delay | Instantaneous |
| Ambient air temperature for operation | -25...60 °C |
MPN