The Schneider Electric A9R56225 is a 2-pole residual current circuit breaker (RCCB) from the Acti9 iID K series, rated 25 A with 300 mA earth-leakage sensitivity. Rated operational voltage is 220…240 V AC 50/60 Hz; insulation voltage is 440 V AC.
Clip-on mounting to DIN rail, 36 mm width (4 x 9 mm pitches), 85 mm height, 69 mm depth. Neutral on the left. Tunnel terminals accept 1…35 mm² rigid or 1…25 mm² flexible; tightening torque 3.5 N.m.
Designed and certified to EN/IEC 61008-1 and EN/IEC 61008-2-1 (residual current operated circuit-breakers without integral overcurrent protection). Carries the NF quality label. Pollution degree 2, electromagnetic compatibility with 8/20 µs impulse withstand at 200 A per EN/IEC 61008-1. Mechanical durability 5000 cycles; electrical durability (AC-1) 2000 cycles.