Skip to main content
Schneider Electric A9R62240 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9R62240 Acti9 iID RCCB, 40 A, 100 mA, Ty

MPNA9R62240
Obsolete

Schneider Electric Acti9 iID RCCB, 2P, 40 A, 100 mA sensitivity, Type AC, 230-240 V AC, DIN rail clip-on.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9R62240 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)100 mA
Earth-leakage protection class / typeType AC
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
A9R62240 — Electrical Ratings
ParameterValue
Rated current (In)40 A
Rated operational voltage (Ue)230...240 V AC 50/60 Hz
Poles description2P
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)6 kV
Device location in systemOutgoer
Electrical durabilityAC-1: 15000 cycles
Mechanical durability (operating cycles)20000 cycles
A9R62240 — Identification
ParameterValue
Product nameActi9 iID
Product / component typeResidual current circuit breaker (RCCB)
Product range / familyActi9
Device short nameiID
A9R62240 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsSingle terminal top or bottom 1...35 mm² rigid Single terminal top or bottom 1...25 mm² flexible Single terminal top or bottom 1...25 mm² flexible with ferrule
Wire stripping length14 mm for top or bottom connection
Terminal tightening torque3.5 N.m top or bottom
Width36 mm
Height96 mm
Depth74.5 mm
A9R62240 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3
A9R62240 — Approvals
ParameterValue
StandardsGB 16916.21

Product details

It's rated 40 A continuous, with 100 mA sensitivity, Type AC (sinusoidal AC residual currents only). That 100 mA threshold makes it a good fit for general-purpose circuits where a higher trip level avoids nuisance tripping from normal leakage, like on distribution boards feeding multiple loads. Breaking capacity is 1500 A (Idm and Im both 1500 A), and insulation voltage is 500 V AC.

The 36 mm width (4 module spaces) fits neatly into a modular enclosure or distribution board. Terminals accept 1 to 35 mm² rigid or 1 to 25 mm² flexible wire; strip length is 14 mm. IP20 on the device body, IP40 inside a modular enclosure — fine for dry indoor panels, not for washdown areas.

Frequently asked questions

Who supplies A9R62240 and how is it quoted for volume purchases?

The A9R62240 is supplied through independent distribution channels. For volume purchases or BOM-line commitments, submit an RFQ — we confirm availability and current pricing at quote time.

What is A9R62240's listed depth?

The A9R62240 has a depth of 74.5 mm, with a width of 36 mm (4 x 9 mm pitches) and height of 96 mm.

What compliance documentation does this RCCB carry?

The A9R62240 is certified to GB 16916.21 (Chinese national standard for RCCBs). It also meets EN/IEC 61008-1 for electromagnetic compatibility (8/20 µs impulse withstand, 250 A). IP ratings are IP20 per IEC 60529 and IP40 in a modular enclosure per IEC 60529.

MPN
A9R62240