Skip to main content
Schneider Electric C063N350FM — Miniature Circuit Breakers (MCB)

C063N350FM ComPacT NS 630A 3P Circuit Breaker, 50 kA at 415V

MPNC063N350FM
Active

Schneider Electric ComPacT NS new generation, 630 A, 3P, MicroLogic 5.0 electronic trip unit, 50 kA at 415 V AC, fixed mount, manually operated.

$2,989.56Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C063N350FM — Identification
ParameterValue
Product nameComPacT NS new generation
Product rangeComPacT
Product range (series)ComPacT NS630b...1600 new generation
Product/component typeCircuit breaker
Device applicationDistribution
C063N350FM — Ratings
ParameterValue
Rated current (In)630 A at 50 °C
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory B
Overvoltage categoryIII
C063N350FM — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)2000 cycles at 690 V In 4000 cycles at 690 V In/2 5000 cycles at 440 V In 6000 cycles at 440 V In/2
Mechanical durability (cycles)10000 cycles
C063N350FM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeManually operated
Local signalling/indication4 LEDs (red) for fault indication 1 LED (yellow) for overload
C063N350FM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
Relative humidity0...95 %
C063N350FM — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C063N350FM — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.4...1 x In
Trip unit protection functionsLSI

Product details

The C063N350FM is a Schneider Electric ComPacT NS new generation 3-pole molded case circuit breaker (MCCB) rated 630 A at 50 °C, fitted with a MicroLogic 5.0 electronic trip unit offering LSI protection — long-time overload (L), short-time short-circuit (S), and instantaneous short-circuit (I). It's a manually operated, fixed-mount unit for distribution applications, compliant with EN/IEC 60947-2. The 50 kA breaking capacity code at 415 V AC (85 kA Icu at 240 V) gives you solid fault-clearing headroom for most industrial panel feeds.

Push it to 60 °C and you'll need to consult the thermal derating curve. For the service breaking capacity (Ics), expect 100% of Icu on this class — meaning it can clear a 50 kA fault and be immediately reclosed, which matters for coordination studies. The MicroLogic 5.0 trip unit is fully electronic, so you get adjustable L, S, and I curves via the front dials — no thermal bimetal drift over time. The 20-minute thermal memory means the breaker remembers prior heating events and shortens the trip time on a reclose, which is useful for motor starting or capacitor bank switching where repeated inrush occurs. The 10,000 mechanical cycles and 2,000 electrical cycles at rated current tell you this is a distribution breaker, not a switching device for daily motor starts. If you need frequent load switching, look at a contactor upstream. The IP40 front-face protection means it's splash-proof from the front but not sealed — mount it inside a panel rated for the environment. The IK07 impact rating handles accidental tool drops during maintenance.

Integration notes

Fixed-mount on a backplate — no DIN rail adapter on this frame size. The 210 mm width and 327 mm height need a cutout or mounting plate sized accordingly. Front connection both upstream and downstream with a 70 mm connection pitch — standard for busbar or cable lug termination. The manually operated control means no motor operator or shunt trip included; those are optional accessories.

Frequently asked questions

What is C063N350FM's breaking capacity at 415 V?

50 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. The service breaking capacity (Ics) is typically 100% of Icu on this class.

What trip unit does C063N350FM use?

It uses a MicroLogic 5.0 electronic trip unit with LSI protection — long-time (L), short-time (S), and instantaneous (I) adjustable curves. No earth-leakage protection is included.

Where can I buy C063N350FM?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN