Skip to main content
Schneider Electric C063N35EFM — Miniature Circuit Breakers (MCB)

C063N35EFM ComPacT NS 630A 3P MCCB, MicroLogic 5.0 E, 50 kA

MPNC063N35EFM
Active

Schneider Electric ComPacT NS new generation, C063N35EFM, 3-pole 630 A MCCB with MicroLogic 5.0 E electronic trip unit, 50 kA Icu at 415 V AC, fixed mount, IP40.

$2,701.66Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C063N35EFM — Identification
ParameterValue
Product nameComPacT NS new generation
Product rangeComPacT
Product range (series)ComPacT NS630b...1600 new generation
Product/component typeCircuit breaker
Device applicationDistribution
C063N35EFM — Ratings
ParameterValue
Rated current (In)630 A at 50 °C
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory B
Overvoltage categoryIII
C063N35EFM — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)2000 cycles at 690 V In 4000 cycles at 690 V In/2 5000 cycles at 440 V In 6000 cycles at 440 V In/2
Mechanical durability (cycles)10000 cycles
C063N35EFM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeManually operated
Local signalling/indication4 LEDs (red) for fault indication 1 LED (yellow) for overload
C063N35EFM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
Relative humidity0...95 %
C063N35EFM — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C063N35EFM — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.4...1 x In
Trip unit protection functionsLSI

Product details

The C063N35EFM is a 3-pole 630 A molded-case circuit breaker from Schneider Electric's ComPacT NS new generation line, fitted with a MicroLogic 5.0 E electronic trip unit. It's a distribution-grade breaker (category B per IEC 60947-2) with an energy-metering function built into the trip unit — so it reports consumption data through the LCD display, not just trips. The 630 A rating at 50 °C means it carries full current in a warm panel without derating; above that ambient you'd need to consult the thermal curve.

MicroLogic 5.0 E gives you LSI protection — long-time overload (L), short-time short-circuit (S), and instantaneous (I) — plus the energy-metering function that tracks kWh, power, and demand through the LCD. The thermal memory holds for 20 minutes after a trip, so it remembers the heat profile if you reclose quickly on a hot breaker. That matters for motor or transformer feeders where repeated starts can accumulate heat. The electronic trip is field-adjustable, so you can dial in the pickup and time bands without swapping the trip unit. No earth-leakage protection on this variant (the E suffix means energy metering, not earth fault).

Fixed mount on a backplate — no draw-out cradle, no DIN-rail clip. The 210 mm width, 327 mm height, and 147 mm depth are the envelope you need to clear in the enclosure. Connection pitch is 70 mm between poles, front-connected both top and bottom, so busbar or cable routing is straight in and out. IK07 impact rating means it survives a hammer knock during panel work. Pollution degree 3 per IEC 60947 — it's rated for conductive environments, not just clean control rooms.

Operating altitude rated to 2,000 m without derating, 2,000 to 5,000 m with derating (air density affects arc extinction). Relative humidity 0 to 95% — no condensation concern in normal indoor gear.

Frequently asked questions

What is the breaking capacity of C063N35EFM at 415 V?

50 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. At 220/240 V it's 85 kA Icu; at 690 V it's 30 kA Icu.

What trip unit does C063N35EFM use?

MicroLogic 5.0 E electronic trip unit with LSI protection (long-time, short-time, instantaneous) and integrated energy metering. The LCD display shows metering data and fault indications.

Where can I buy C063N35EFM and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What are the mounting dimensions of C063N35EFM?

210 mm wide, 327 mm high, 147 mm deep. Fixed backplate mount with 70 mm pole pitch. Front-connected top and bottom.

MPN
C063N35EFM