Skip to main content
Schneider Electric C063N4FM — Miniature Circuit Breakers (MCB)

C063N4FM ComPacT NS630bN Basic Frame, 630A 4P, 50kA at 415VA

MPNC063N4FM
Active

Schneider Electric ComPacT NS630bN new generation basic frame, C063N4FM, 630 A at 50 °C, 4 poles, fixed mount, manually operated, 50 kA breaking capacity at 415 V AC.

$1,563.78Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C063N4FM — Identification
ParameterValue
Product rangeComPacT
Product range (series)ComPacT NS630b...1600 new generation
Product/component typeBasic frame
Device applicationDistribution
C063N4FM — Ratings
ParameterValue
Rated current (In)630 A at 50 °C
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory B
Overvoltage categoryIII
C063N4FM — Protection
ParameterValue
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)2000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2 4000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2 5000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2 6000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2
Mechanical durability (cycles)10000 cycles conforming to IEC 60947-2
C063N4FM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeManually operated
C063N4FM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
C063N4FM — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

Basic frame for a distribution breaker

The C063N4FM is a basic frame in the ComPacT NS630b...1600 new generation range — a manually operated, fixed-mount 4-pole chassis rated 630 A at 50 °C. It ships without a protection control unit or trip block; the buyer selects and installs the electronic or micrologic trip separately to define overcurrent, ground-fault, and zone-selective interlocking behavior. This is standard practice for high-current frames where the trip curve must match the load profile (transformer, feeder, generator). The frame itself carries the full interrupting duty: 50 kA Icu at 415 V AC, 85 kA at 240 V, tapering to 30 kA at 690 V — all per IEC 60947-2, category B (unlimited selectivity). Mounting is fixed to a backplate via 70 mm connection pitch. Neutral is on the left. The front face offers Class II shock protection; the enclosure is IP40 with IK07 impact resistance.

Breaking capacity and service continuity

For most distribution boards fed by a 1 MVA or smaller transformer, 50 kA at 415 V provides adequate fault clearance. The Ics matches Icu at 415 V — 50 kA — so the breaker can be reclosed immediately after clearing a fault at that voltage without derating, per IEC 60947-2. At 690 V, Ics equals Icu at 30 kA.

Fixed backplate mount, 280 mm wide × 224 mm tall × 147 mm deep. The 70 mm pole-to-pole pitch is standard for busbar connection in switchboards. Power dissipation is 10 W at rated current — negligible for enclosure thermal rise but worth noting if the cubicle is densely packed.

Frequently asked questions

What is the breaking capacity of C063N4FM at 415 V?

The C063N4FM frame is rated 50 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2, with the same 50 kA Ics for immediate reclose after fault clearance at that voltage.

What does 'basic frame' mean on the C063N4FM?

A basic frame ships without a trip unit or protection control module. The buyer installs a separate electronic or micrologic trip to set overcurrent, ground-fault, and zone-selective interlocking parameters. The frame itself provides the mechanical switching and interrupting structure.

MPN
C063N4FM