Skip to main content
Schneider Electric C063N420FM — Miniature Circuit Breakers (MCB)

Schneider Electric C063N420FM ComPacT NS630b 630A 4P MCCB, 5

MPNC063N420FM
Active

Schneider Electric ComPacT NS new generation, C063N420FM, 630 A, 4P, MicroLogic 2.0 electronic trip unit, 50 kA Icu at 415 V AC, fixed mount, front connection.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C063N420FM — Identification
ParameterValue
Product nameComPacT NS new generation
Product rangeComPacT
Product range (series)ComPacT NS630b...1600 new generation
Product/component typeCircuit breaker
Device applicationDistribution
C063N420FM — Ratings
ParameterValue
Rated current (In)630 A at 50 °C
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory B
Overvoltage categoryIII
C063N420FM — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)2000 cycles at 690 V In 4000 cycles at 690 V In/2 5000 cycles at 440 V In 6000 cycles at 440 V In/2
Mechanical durability (cycles)10000 cycles
C063N420FM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeManually operated
Local signalling/indication4 LEDs (red) for fault indication 1 LED (yellow) for overload
C063N420FM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
Relative humidity0...95 %
C063N420FM — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C063N420FM — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.4...1 x In
Trip unit protection functionsLI

Product details

The C063N420FM is a Schneider Electric ComPacT NS new generation moulded-case circuit breaker, rated 630 A at 50 °C with a MicroLogic 2.0 electronic trip unit. It is a 4-pole, fixed-mount unit with front connections, designed for distribution applications in commercial and industrial switchboards. The breaker is manually operated and complies with EN/IEC 60947-2, which governs low-voltage switchgear and controlgear — specifically the requirements for circuit-breaker performance and coordination.

The breaking capacity is 85 kA Icu at 220/240 V AC, 50 kA at 380/415 V AC, and 40 kA at 500/525 V AC. That figure governs selectivity with upstream devices and determines whether the panel's SCCR is met. The utilisation category is Category B, meaning the breaker is suitable for selective coordination — it can be set to let downstream faults clear first, keeping supply to healthy circuits.

The MicroLogic 2.0 electronic trip unit provides L (long-time overload) and I (instantaneous short-circuit) protection. The thermal memory is 20 minutes, which prevents nuisance tripping on repeated overloads by retaining heat history. The trip unit is rated 630 A at 50 °C; if the ambient in your enclosure runs hotter, expect derating. The breaker includes local signalling via four red LEDs for fault indication and one yellow LED for overload — useful for a quick visual check during commissioning or troubleshooting without opening the panel.

Fixed-mount on a backplate, with front connections top and bottom. Dimensions: 327 mm high, 280 mm wide, 147 mm deep. Connection pitch is 70 mm. The IP40 enclosure protection means it is safe from tools and small wires but not from water — keep it inside a dry switchboard. IK07 impact resistance handles accidental knocks during panel assembly.

Frequently asked questions

What is the breaking capacity of C063N420FM at 415 V?

50 kA Icu at 380/415 V AC, 50/60 Hz, per IEC 60947-2.

What trip unit does C063N420FM use?

It uses a MicroLogic 2.0 electronic trip unit providing L (long-time overload) and I (instantaneous short-circuit) protection.

How do I get pricing and availability for C063N420FM?

Submit an RFQ through the storefront. Availability and current pricing are confirmed at quote time.

MPN