Skip to main content
Schneider Electric C080L3WM — Miniature Circuit Breakers (MCB)

Schneider Electric C080L3WM ComPacT NS800L, 800A, 3P, 150kA

MPNC080L3WM
Active

Schneider Electric ComPacT NS800L new generation, basic frame C080L3WM, 800 A at 50 °C, 150 kA Icu at 415 V AC, 3P, withdrawable, manually operated, without control unit.

$2,836.16 – $5,947.56Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C080L3WM — Identification
ParameterValue
Product rangeComPacT
Product range (series)ComPacT NS630b...1600 new generation
Product/component typeBasic frame
Device applicationDistribution
C080L3WM — Ratings
ParameterValue
Rated current (In)800 A at 50 °C
Breaking capacity150 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 150 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 130 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)150 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 150 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 130 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C080L3WM — Protection
ParameterValue
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)2000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2 3000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2 3000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2 4000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2
Mechanical durability (cycles)10000 cycles conforming to IEC 60947-2
C080L3WM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeWithdrawable
Control typeManually operated
C080L3WM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
C080L3WM — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

The C080L3WM is a basic frame — the structural and contact assembly — for the ComPacT NS800L new-generation circuit breaker. It is rated 800 A at 50 °C and carries a 150 kA Icu at 415 V AC, which means it can safely interrupt fault currents up to that level on a 415 V distribution bus without the arc flashing over. The frame is 3-pole, withdrawable, and manually operated; it ships without a control unit or protection trip module, so you select the appropriate Micrologic trip unit separately to match your coordination study.

The L breaking-capacity code delivers 150 kA Icu at 380/415 V AC and 130 kA at 440 V AC. The Ics — the service breaking capacity — matches the Icu at every voltage point, so the breaker can be reclosed after a fault at its full rating without derating. For selectivity studies, the Icw is 19.2 kA for 1 s, giving downstream devices time to clear a fault before the main trips. The frame is rated Category A, meaning it is not intended for deliberate short-time delay coordination — pair it with a Micrologic trip unit that provides the delay.

The frame mounts on a backplate in a withdrawable configuration — the breaker chassis stays fixed while the moving portion can be racked out for maintenance or replacement without disturbing the bus connections. Connection pitch is 70 mm. Dimensions: 260 mm high, 236 mm wide, 147 mm deep. The front face is Class II shock-protected, and the enclosure is rated IP40 with an IK07 impact rating.

Environmental and durability

Power losses at rated current are 40 W. Mechanical durability is 10,000 cycles; electrical durability varies by voltage and current — for example, 2,000 cycles at 690 V at full In, and 4,000 cycles at 440 V at In/2.

Frequently asked questions

Who supplies C080L3WM and how is it quoted for volume purchases?

The C080L3WM is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is C080L3WM's breaking capacity at 415 V?

The C080L3WM delivers 150 kA Icu at 380/415 V AC 50/60 Hz, with the Ics matching the Icu at that voltage.

What compliance standards does C080L3WM meet?

The frame is designed and tested to IEC 60947-2. It is suitable for isolation per EN/IEC 60947-2, carries pollution degree 3, overvoltage category III, and the front face is Class II shock-protected.

MPN
C080L3WM