Skip to main content
Schneider Electric C080L4WM — Miniature Circuit Breakers (MCB)

Schneider Electric C080L4WM ComPacT NS800L, 800A 4P Drawout,

MPNC080L4WM
Active

Schneider Electric ComPacT NS800L new generation, basic frame C080L4WM, 800 A at 50 °C, 4-pole drawout, manually operated, 150 kA Icu at 415 V AC, without control unit.

$7,539.48Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C080L4WM — Identification
ParameterValue
Product rangeComPacT
Product range (series)ComPacT NS630b...1600 new generation
Product/component typeBasic frame
Device applicationDistribution
C080L4WM — Ratings
ParameterValue
Rated current (In)800 A at 50 °C
Breaking capacity150 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 150 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 130 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)150 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 150 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 130 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C080L4WM — Protection
ParameterValue
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)2000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2 3000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2 3000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2 4000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2
Mechanical durability (cycles)10000 cycles conforming to IEC 60947-2
C080L4WM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeWithdrawable
Control typeManually operated
C080L4WM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
C080L4WM — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

ComPacT NS800L basic frame – 800 A, 4P drawout

The C080L4WM is a basic frame from the Schneider Electric ComPacT NS630b…1600 new generation range — a 4-pole, manually operated, withdrawable air circuit breaker frame rated 800 A at 50 °C. It carries no integral protection (no trip unit), so it is the chassis you build a distribution breaker around: you add a compatible Micrologic control unit to set the protection curves. Breaking capacity is the headline here: 150 kA Icu at 415 V AC, 130 kA at 440 V, and 100 kA at 500/525 V — all per IEC 60947-2. That puts it in the high-fault tier for industrial main switchboards and large distribution panels where fault currents can exceed 100 kA. The Ics (service breaking capacity) matches the Icu values at the same voltages, meaning the breaker can be reclosed after a fault at full rating without derating. Withdrawable (drawout) mounting means the breaker chassis stays bolted to the backplate while the moving portion racks out for inspection or swap — no need to disconnect main power cables. The neutral pole is on the left; connection pitch is 70 mm.

If your panel runs hotter, you derate per the manufacturer's curve — but the frame itself is sized for the full 800 A in typical switchroom conditions. The 40 W power loss figure tells you the heat the frame dissipates at rated current; factor that into your enclosure ventilation calcs. Impulse withstand (Uimp) is 8 kV, which covers overvoltage category III installations. Mechanical durability is 10,000 cycles; electrical durability varies by voltage and current — 2,000 cycles at 690 V at In, 4,000 cycles at 440 V at In/2. That is typical for a drawout frame in distribution service where it operates a few times a year, not daily switching.

Mounts on a backplate via the withdrawable cradle. The frame is 306 mm wide, 260 mm high, 147 mm deep — substantial, but standard for an 800 A drawout. IP40 front face protection; IK07 impact resistance. The front face is Class II insulated (no earth connection needed on the operator side). The integral instant protection rating of 40 kA is a mechanical withstand figure for the frame itself when no trip unit is installed — the actual protection setting comes from the control unit you add.

Because this is a basic frame without a control unit, verify that the Micrologic trip unit you plan to use is compatible with the NS800L frame. The frame accepts the same plug-in control units as the rest of the NS630b…1600 range.

Frequently asked questions

Where can I buy the C080L4WM and get current pricing?

The C080L4WM is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What breaking capacity does the C080L4WM have at 415 V?

150 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. The Ics (service breaking capacity) is the same 150 kA at that voltage, so the breaker can be reclosed after a full-rated fault without derating.

What compliance standards does the C080L4WM meet?

It is designed and tested to IEC 60947-2 for circuit breakers. The front face carries Class II shock protection. Pollution degree 3, overvoltage category III, and IK07/IP40 enclosure ratings are all per the relevant IEC/EN standards.

Does the C080L4WM include a trip unit?

No — this is a basic frame (without protection). You must add a compatible Micrologic control unit to set the protection curves. The frame accepts the same plug-in control units as the rest of the NS630b…1600 range.

MPN
C080L4WM