Skip to main content
Schneider Electric C080L4FM — Miniature Circuit Breakers (MCB)

Schneider Electric C080L4FM ComPacT NS800L, 800A 4P Fixed, 1

MPNC080L4FM
Active

Schneider Electric ComPacT NS800L new generation, basic frame C080L4FM, 800 A at 50 °C, 4P fixed, manually operated, 150 kA Icu at 415 V AC, IEC 60947-2.

$2,601.22 – $3,440.31Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C080L4FM — Identification
ParameterValue
Product rangeComPacT
Product range (series)ComPacT NS630b...1600 new generation
Product/component typeBasic frame
Device applicationDistribution
C080L4FM — Ratings
ParameterValue
Rated current (In)800 A at 50 °C
Breaking capacity150 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 150 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 130 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)150 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 150 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 130 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C080L4FM — Protection
ParameterValue
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)2000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2 3000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2 3000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2 4000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2
Mechanical durability (cycles)10000 cycles conforming to IEC 60947-2
C080L4FM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeManually operated
C080L4FM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
C080L4FM — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

Frame and breaking capacity

The C080L4FM is a ComPacT NS800L basic frame from the new-generation NS630b…1600 range, rated 800 A at 50 °C and carrying a 150 kA Icu at 380/415 V AC — the L breaking-capacity code. The frame is 4-pole, fixed-mounted to a backplate, manually operated, and ships without a protection control unit — it is the mechanical base that accepts a separate trip unit (ordered by the buyer to match the protection curve needed).

The Ics (service breaking capacity) matches the Icu at every voltage level, meaning the breaker can be reclosed after clearing a fault at its full rating without derating — a practical advantage for industrial plants that cannot tolerate a prolonged outage after a fault event. The 4-pole configuration with neutral on the left is fixed — the neutral pole is not switched by the trip unit unless a 4-pole control unit is installed.

Fixed backplate mounting with a 70 mm connection pitch. The 20 W power loss at rated current should be factored into the panel thermal budget.

Designed and tested to IEC 60947-2, with an 8 kV rated impulse withstand voltage (Uimp) and a 19.2 kA / 1 s short-time withstand current (Icw). Overvoltage category III, utilisation category A. Electrical durability ranges from 2000 to 4000 cycles depending on voltage and current level; mechanical durability is 10 000 cycles. Storage temperature range -50 to 85 °C, operating -25 to 70 °C.

Frequently asked questions

What is the breaking capacity of C080L4FM at 415 V?

150 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. The Ics (service breaking capacity) is the same 150 kA at that voltage, so the breaker can be reclosed after clearing a full-rated fault.

Does C080L4FM include a trip unit?

No — this is a basic frame (product type 'basic frame') without a protection control unit. The trip unit must be ordered separately to set the overload and short-circuit protection curve.

Where can I buy C080L4FM and how is it quoted?

Sourced through the Schneider Electric authorized channel and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time through independent distribution.

What standards does C080L4FM comply with?

IEC 60947-2 for low-voltage switchgear and controlgear. It also carries an isolation suitability marking per EN/IEC 60947-2 and a Class II shock protection rating on the front face.

MPN